Part a Sitc of Ups and Batt. Bank, Qty: 5 Job, (BOQ Item #1) Tender, Delhi (NCT) - 99929493

BHARAT SANCHAR NIGAM LIMITED (BSNL) has floated a tender for Part a Sitc of Ups and Batt. Bank, Qty: 5 Job, (BOQ Item #1). The project location is New Delhi, Delhi (NCT), India. The reference number is GEM/2024/B/4854595 and it is closing on 01 May 2024. Suppliers can request Register free of cost to get the complete Tender details and download the document.

Expired Tender

Procurement Summary

State : Delhi (NCT)

Summary : Part a Sitc of Ups and Batt. Bank, Qty: 5 Job, (BOQ Item #1)

Deadline : 01 May 2024

Other Information

Notice Type : Tender

TOT Ref.No.: 99929493

Document Ref. No. : GEM/2024/B/4854595

Competition : NCB

Financier : Self Financed

Purchaser Ownership : Public

Document Fees : Refer Document

Tender Value : Refer Document

EMD : ₹ 220511

Purchaser's Detail

Purchaser : BHARAT SANCHAR NIGAM LIMITED (BSNL)
Ministry Of Communications
Department of Telecommunications (DOT)
Surender Singh Khatri 110001, Eastern Court, Janpath, New Delhi 5 90 Part A SITC Of UPS And Batt. Bank
Bsnl Electrical Zone New Delhi
Country: India
Email: surenderkhatri@bsnl.co.in
Website: www.gem.gov.in

Tender Details

BOQ Item Description: 1.1 SITC of 80KVA rating UPS working in parallel config. 4plus1 and having the foll specs.in addition to detailed specs.
a True online double conversion 3 Level IGBT Rectifier and IGBT Inverter with internal modu. const. Microprocessor based UPS for 3 ph IP 3 ph OP.
b Mains IP V is 415V Selectable at 50Hz freq.. V rage shall be minus15prcnt to plus20prcnt from normal at 100prcnt load or better and minus50prcnt to plus20prcnt from normal at 50prcnt load or better. IP power factor 0.99 at 100prcnt linear load IP THDi 5 prcnt at 100 prcnt linear load.
c UPS sys shall have an OP Power Factor 0.9 at 415 V Selectable and 50Hz freq.
d In all modes of UPS op. the inverter must draw power through batt. only.
e OP THD shud be less than 3prcnt for full linear load and Less than 5prcnt for non linear load.
f OL upto 111 to 125prcnt for 10 min 126 to 150prcnt for 1 min and shud be able to operate cont at 115prcnt load on bypass mode.
g Parallel comm. port RS232 USB EPO and SNMP interface BMS interface Dust Filter at Air Inlet pt are reqd.
h UPS sys shall be able to work in parallel upto minimum 6units for enhanced cap. in future.
i LCD Disp. indicating all imp. parameters as per specs.
j To improve the UPS Security over LAN WAN the SNMP card provided with UPS shall be having Cyber security enhancements as per IEC standards including stronger encryption configurable PW policy. The card shall work on GB Speed support all major protocols
k UPS shall be provided with Temp Humidity Sensors to monitor Temp and Humidity over LAN through SNMP card Software.
l batt. breaker MCCB in each batt. string, batt. breaker encl. batt. to UPS cable complete as reqd shud be provided with UPS sys. The UPS shud be ready to use with Lithium Ion batt. if reqd in future.
m UPS Datasheet provided is to be filled and submitted aw the Technocommercial bid. UPS Appd Make Schneider Vertiv ABB Numeric Legrand Eaton Labotek Fuji Electric APC Mitsubishi GE.
Items are as per schedule of work item no. 1.1
BOQ Title: SITC of 5 X 80 KVA UPS System
Item Title: Part a Sitc of Ups and Batt. Bank
Item Quantity: 5
Unit of Measure: Job
Delivery Period (In number of days): 90
Start Date: 12-04-2024 11:13 AM
End Date: 01-05-2024 12:00 PM
EMD Amount: 220511

Documents

 Tender Notice

Bid_Document_6304774.pdf

Specification_Document.pdf

BOQ_Document.csv


Gem Services Registration Consultant