Tenders are invited for Work to Upgrade the Security System Phases 2 and 3 of the Hilton Yaoundé CHC.
1. Object
The Managing Director of the Hilton Yaoundé CHC, Contracting Authority, is launching a National Open Call for Tenders for the work to upgrade the phase 2 and 3d security system of the Hilton Yaoundé CHC.
2. Consistency of the services
The works include the following services:
installation of an automatic extinguishing system in the medium voltage transformer / cell room :
- production of as-built drawings and user manuals;
- installation of the system and of all the accessories and elements necessary for its proper functioning, realization of the cabling and installation of pipes and mechanical fittings without welding;
- programming, testing and commissioning by a certified engineer from the manufacturer. Training on the operation and maintenance of the system by the latter.
central security system upgrade:
- installation of all additional components;
- programming, testing and commissioning by a certified engineer from the manufacturer.
checkpoint maintenance:
- checking all the pipes to ensure that there are no obstructions;
- opening the drain valve to ensure that the water flow conforms to the pressure indicated on the pressure gauge;
- verification of alarm connections to the central fire safety system.
replacement of test valves including all suggestions.
replacement of sprinkler heads :
- closing of sprinkler network valves and emptying of the network;
- disassembly of sprinkler heads and storage at rebu t (location to be defined by the Contracting Authority). Replacement of all defective fittings;
- mounting of the new sprinkler heads (Correction of the height when necessary, the discharge mouth must be fully exposed);
- mounting of the rosettes (They must be well fixed) and touch up of paint including all suggestions.
It should be noted that corrections will have to be made to the network as follows:
- the following areas must have additional sprinklers in order to cover the spaces obstructed by beams and the like:
- level 11: Panoramic bar
- level 02: common corridors, store, technical room
- level 01: Sapelli, Ebony and banquet store
- basement: staff cafeteria, laundry room, laundry corridor, lockers
- the following areas have sprinklers too close to the walls:
- level 11: sitting area
- level 01: Banquet kitchen
- ground floor: Former Ringo shop, airline office (Safar Tours), main kitchen
- basement: Laundry room (in the corner); staff kitchen.
Similarly, it should be noted that the distance between a sprinkler head and the nearest wall is 2.3m:
- the following zones have sprinklers too far from each other:
- level 01: main lobby
- basement: parking (7x7m), fitness corridor, recreation room
It should also be noted that the maximum distance between two sprinkler heads is 4.6m:
- the following areas are not sufficiently covered by sprinkler heads. Also a cover must be established respecting the two conditions posed above (2.3 m from the walls and 4.6 at most between two heads):
- customer floors (1 st to 10 th ): Alcove rooms, public toilets, room bathrooms 5.1 m² (for example in the presidential suites, level 8, etc.); toilet and kitchenette in the executive lounge (level 8);
- elevator machine rooms;
- level 02: store in the technical room;
- level 01: main hall near the toilets, translation area between levels 01 and 02;
- ground floor: Waterfall, PCS, operator room, reception desk, end of the outside corridor, casino and shops (last 15 meters), kitchen service area, cold room;
- basement: compressor room, main pump, entrance to swimming pool changing rooms
- the laundry chute must have a sprinkler protection with heads at several levels, but one sprinkler at the highest point and another at the lowest point;
- the distances of certain floor-to-ceiling sprinklers in the areas listed below exceed 300 mm and therefore do not comply with NFPA 13 standard:
- technical room 12 e (about 1500 mm from the ceiling)
- level 02: technical room
- level 01: banquet service corridor (4 to 5 m from the ceiling)
- ground floor: luggage store, F&B store and hall
- basement: some parking lots, Laundry room.
- the distance between the side jets and the ceiling in the executive lounge exceeds 300 mm and therefore does not comply with NFPA 13. This must be revised (approximately 600 mm from the ceiling).
technical assistance by Bureau Veritas to validate the installation: Provide a compliance report and a test certificate.
3. Estimated cost
The estimated cost of the operation after the preliminary studies is one hundred and seventy-eight million eight hundred and seventy-five thousand (178, 875, 000) FCFA including tax .
4. Delivery time
The execution period is nine (09) months. This period runs from the date of notification of the service order prescribing the start of work.
5. Allotment
The works are in a single batch.
6. Participation and origin
Participation in this invitation to tender is open at national level to all companies specializing in building and public works.
7. Financing
The work that is the subject of this invitation to tender is financed by the HILTON Yaoundé CHC investment budget, EXERCISE 2020, on budget allocation line no. P2016 / 11 - P2018 / 06.
8. Consultation of the file
The file can be consulted during working hours at the Public Markets department of the Hilton Yaoundé CHC, BP . 11852, Tel. : 237 222 23 36 46, Fax: 237 222 22 32 10, www.armp.cm as soon as this notice is published.
9. Acquisition of the file
The file can be obtained from the Public Markets department of the Hilton Yaoundé CHC, BP . 11852, Tel. : 237 222 23 36 46, Fax: 237 222 22 32 10, (reservationsyaoundé@hilton.com) upon publication of this notice, against payment of a non-refundable sum of one hundred thousand (100, 000) FCFA, payable to the special CAS account ARMP 335988 ”open in all BICEC branches.
10. Submission of tenders
Each offer written in French or English in seven (07) copies including one (01) original and six (06) copies marked as such, must reach the Public Contracts department of the Hilton Yaoundé CHC no later than 24/03/2020 at 3.30 p.m. precise and must bear the mention:
OPEN NATIONAL CALL FOR TENDERS
N ° 03 / AONO / HILTON / CHC / CIPM / 2020 OF 09 MARCH 2020
RELATING TO THE UPGRADING OF THE PHILASES 2 AND 3 OF THE HILTON YAOUNDÉ CHC SAFETY SYSTEM
To be opened only during the counting session
11. Provisional security
Each tenderer must attach to his administrative documents, a bid bond established by a first-rate bank approved by the Ministry of Finance and whose list appears in Exhibit 12 of the DAO, in the amount of three million five hundred and sixty- seventeen thousand five hundred (3, 577, 500 ) FCFA inclusive of tax and valid for thirty (30) days beyond the original date of validity of the offers.
12. Admissibility of tenders
Under penalty of rejection, the documents in the required administrative file must be produced in originals or certified copies by the issuing service or an administrative authority (Prefect, Sub-prefect, ), in accordance with the provisions of the Supplementary Regulations of the Invitation to Tender.
They must date from less than three (03) months preceding the original date of submission of tenders or have been established after the date of signature of the Invitation to Tender.
Any incomplete offer in accordance with the prescriptions of the Tender File will be declared inadmissible. In particular the absence of the bid bond issued by a first class bank approved by the Ministry of Finance.
The authorized publication medium is the ARMP Market Journal (JDM).
NB: No distinctive mention must appear on the offer. To this end, tenderers are requested to take all the relevant provisions.
13. Opening of bids
The folds will be opened in one step. The opening of administrative documents, technical and financial offers will take place on 03/24/2020 at 4.30 p.m., by the CHC`s Internal Procurement Commission at the Hilton Yaoundé CHC.
Only tenderers may attend this opening session or be represented by a person of their choice duly authorized.
14. Evaluation criteria
1. Elimination criteria
a) absence of the bid bond;
b) incomplete technical offer for:
false declaration or forged document;
non-compliance with major technical specifications (non-compliance with one of the characteristics of the equipment);
absence of manufacturer`s authorization;
absence of technical data sheets or flyers for equipment (Sprinklers, test valves, safety systems);
have not met at least eighteen (18) of the twenty-four (24) essential criteria;
c) financial offer
absence of a quantified unit price;
insufficient financial surface (CFAF 53, 662, 500 including VAT Minimum).
2. Essential criteria
The evaluation of technical and financial offers will be made on the basis of the essential criteria below:
a) presentation of the offer: 2 criteria ;
b) experience: References of the company in building and public works or similar achievements (1 st and last pages of the letters-commands) + Acceptance report corresponding to the services provided (minimum acceptable at least four (04) references during the last three years): 4 criteria ;
c) personnel (certified true copy of the diploma + CV signed and dated by the holder, certificate of availability, experience of the supervisory staff): 9 criteria ;
d) material and logistical means (4 x 4 liaison vehicles or pick-up, availability of essential materials and equipment): 2 criteria ;
e) certificate of site visit signed on honor by the tenderer: 2 criteria ;
f) methodology and organization: 3 criteria;
g) Book of Special Administrative Clauses (CCAP), completed, initialed on each page, signed and dated to the last: 1 criterion ;
h) Book of Special Technical Clauses (CCTP) initialed on each page, signed and dated to the last: 1 criterion .
15. Attribution
The Director General Hilton Yaoundé CHC will award the Contract to the tenderer who has presented the lowest evaluated financial offer, essentially complying with the prescriptions of the Tender Documents, having satisfied 100% of the eliminatory criteria and at least 75% of the criteria. essentials.
Any offer not presented in three (03) volumes will be purely and simply rejected; the same applies to any offer that does not comply with the Special Rules of the Call for Tenders (RPAO).
16. Period of validity of tenders
Bidders remain bound by their offer for ninety (90) days from the deadline set for the submission of offers.
17. Additional information
Additional information can be obtained during working hours at the Technical Department and the Market Department of the Hilton Yaoundé CHC, BP 11852, Tel. : 237 222 23 36 46, Fax: 237 222 22 32 10, E- mail :
[email protected],
[email protected] . A visit to the work site is scheduled from to between 11 am sharp at the Technical Department of the Hilton Yaoundé CHC.