Tenders are invited for Supply and Installation of Power Systems for KTRN-S LTE Tower Sites.
Supply and Installation of Power Systems for KTRN-S LTE Tower Sites
KT Rwanda Networks Ltd
KT Rwanda Networks Ltd is the only 4G LTE infrastructure company in Rwanda, jointly invested by the Government of Rwanda and kt exclusively for wholesale provision of universal mobile broadband network in Rwanda using 4G LTE technology.
Website:
http://www.ktrn.rw
Title: SUPPLY AND INSTALLATION OF POWER SYSTEMS FOR KTRN-S LTE TOWER SITES
Tender No: KTRN/ADMIN/M/2020/08/004 Date of issue: August 20, 2020
Date of bid submission: August 28, 2020 Time: 11:00 AM
Introduction
KTRN is the only 4G LTE infrastructure company in Rwanda, jointly invested by the Government of Rwanda and Korea Telecom (KT) exclusively for the wholesale provision of the universal mobile broadband network in Rwanda using 4G LTE technology. The wholesale network service for mobile broadband will help to promote healthy competition for advanced retail services and solutions and will benefit consumers, enterprises, and the nation in transforming Rwanda into the ICT hub of East Africa.
SCOPE OF WORK: SUPPLY AND INSTALLATION OF POWER SYSTEMS FOR KTRN-S LTE TOWER SITES
A. DIESEL SILENT GENERATORs (Original Catalogues required)
GENSET DETAILS / Quantity required: 1 Pc
Generator Type Canopy General Logic or PRAMAC Generators
Gen-set Type Diesel Silent generator type with Auto, Manual, and Test Start system features (Soundproof Type Generators) and lockable doors (front and rear sides)
Capacity 13.5KW / 15 KVA
Connections - Three Phases, 4wires character
- Output: 230 / 400Volts AC, 50Hz / 60Hz
Rated Power 13.5 KW
Rated Frequency 50-60 Hz
Parameters 50hz, 3ph, 400/230v, 1500rpm
Fuel Consumption ≤ 1.5 L/hour
Tank Capacity 1, 000 L (Generator should be mounted on top of fuel tank/access to the tank through generator case)
Noise Level 65-100 (db)
Auto-switching option Generators should be equipped with ATS (Automatic Transfer switch) for Auto-switching from mains to generator supplies
Fuel sensing Generator controllers should have fuel sensors to display additional and level of fuel in the tank
Remote control 4G Modem required for the controller to be remotely accessed (through GPRS or any off-site accessibility)
ENGINE DETAILS
Engine Brand Perkins or Cummins
Cooling System Water Cooled
Speed Governor Electrical
ALTERNATOR DETAILS
Alternator Brand Stamford / Brushless Alternator
Exciter Type Self- excitation, Brushless with AVR
Insulation Class H (strongly complying with outdoor environmental critical conditions)
Protection Grade IP21
PACKAGE
Package 1 SET/Plywood case
Spare parts (Option) If engine brand is not Perkins or Cummins ( Please provide cost of consumable parts for one year maintenance period / 3 terms, excluding ones covered in the first warranty maintenance)
Delivery Propose any convenient time
Warranty At 1500hours / 1 year warranty including first general maintenance service
B. OUTDOOR RECTIFIERs (Original Catalogues required)
The outdoor power rectification system should rectify 160-240v AC power into +/- 48v DC power with internal batteries that provides backup time for 8-10 hours.
Product features
Modular DC/DC converters
Low volume and weight
System power scalability
Hot-Plug rack-mounted power modules design for reliable operation
The easy design of redundant system solutions
High energy capability with good efficiency
Galvanic isolation between input and output
Control, monitoring, and voltage/Amps indication
Minimum Technical Specifications
OUTDOOR RECTIFIER DETAILS / Quantity required: 2 Pcs
Recommended Type Outdoor DELTA -48Voltage DC rectifier systems
INPUT
Voltage (nominal) Three-phase; VL-L: 380VAC; VL-N: 220VAC; 5W (L1, L2, L3, N, PE)
Voltage Three-phase; VL-L: 380/400/415 (±20%); VL-N: 220/230/240 (±20%)
Frequency 45 - 66Hz
OUTPUT
Voltage (nominal) -54VDC
Voltage (default) -54VDC
Voltage (adjustable range) -43 to -58VDC
Maximum Power @ nominal Input 17.4kW from rectifier;
13.2kW from PV charger
BATTERY
Battery characteristics Deep cycling (Long discharge)
Battery Type Northstar or Powersafe
Battery capacity 12V / 190AH
Battery String 2 strings (8 batteries)
Battery Terminal T
MECHANICAL
Dimensions (W x H x D) 800 x 2060 x 750mm (31.49 x 81.10 x 29.52in)
Weight approx. 170kg (374.78Ib) (without a rectifier, external, cooling unit )
IP Protection IP 55
ENVIRONMENTAL
Operating Temperature 0 to +50 ᵒC (32 to +122 ᵒF)
Storage Temperature -40 to +70 ᵒC (-40 to +158 ᵒF)
Altitude 0 to +3000m
Related Humidity 95%, non-condensing (Max.)
Acoustic Noise ≤ 65dBA
Cooling Air-con.: 1333W (L35/35), 1200W (L35/40); Fan: 250W/K
STANDARDS
Safety IEC/EN60950
EMC EN 300 386 / Conduction: class A / Radiation: class B
Environment RoHS
System Redundancy Redundancy technology with two spare power modules (Option)
Display Digital meters
Remote control Voltage and current display, on/off, adjustment of output value
Remote control ports LAN/NMS/RS232/RS485
Inbuilt Protection. Phase loss, input under-voltage, overvoltage, output under-voltage, overcurrent, overheat, short circuit
Cabinet Single cabinet, sealed from corrosive dust and moisture
Working mode 24hours / 7days long time full load continuous operation
Warranty 2 years from delivery against manufacturing defects, material defects and workmanship fails.
C. OUTDOOR AUTOMATIC VOLTAGE REGULATOR 30KVA (Original Catalogues required)
Equipped with user-friendly large-screen LCD display, able to display all of the system voltage, work current, status, and other information.
OUTDOOR AVR DETAILS / Quantity required: 2 Pcs
Operation method Intelligent Voltage Regulator (IVR)
Recommended Type Outdoor DELTA AVR with advanced intelligent control
Phase 3Phase System
Rated Capacity 30KVA
INPUT
Nominal Voltage 220V/230V/240V/254V or 380V/400V/415V/440V
Voltage Regulation Range (±15%, ±20%, ±30% or Customized)
Frequency 50Hz or 60Hz ±5Hz
Input Power Factor 0.98
Applicable Loads Resistive, Capacitive, Inductive Loads
OUTPUT
Nominal Voltage 380V/400V - 415V/440V
Voltage Accuracy Preset at ±1.5% (±2%~±10% Adjustable)
Response Time /= 95%
Overload Ability 150% / 90Seconds - 200% / 20Seconds
LCD TOUCH PANEL DISPLAY
Power Supply Status Mains Supply / Bypass Supply / Generator Supply
Working Status Voltage Regulation/Bypass, Status includes Input Open Phase, Output Open Phase, Input High/Low Voltage, Output High/Low Voltage, Output Overload, Abnormal Transmission, Circuit Abnormal, Door Open, Dis-connected Neutral Line, Phase Sequence Error
Cooling System Normal / Abnormal
System Resume Time Last Resume Time (Mains Regulation function)
Accumulated Runtime Switchable to the recent outage time
Operation Status Auto / Manual (Boost↑, Buck↓)
PROTECTION & ALARM
Input High / Low Voltage LCD Display + Buzzer + Flash Light
Output High / Low Voltage LCD Display + Buzzer + Flash Light + Output Cutoff
Output Open Phase LCD Display + Buzzer + Flash Light + Output Cutoff
Output Overload Circuit Detection Settable + LCD Display + Buzzer + Flash Light
Short Circuit Input Circuit Breaker Cutoff
Manual Bypass Double Throw Bypass Switch (Option: Automatic Bypass)
Soft Start 0~5 Seconds Adjustable
SAFETY
Insulation Resistance /= 5MΩ (Coil to Earth)
Grounding Resistance 0.1mΩ
coil temperature rating class f, 155°c
cooling mode air-forced cooling fan
environment
audible noise 60db at 1m distance with full load
operation environment -5℃~40℃ / 0% ~90% (non-condensing)
operation altitude 1, 000m
remote monitoring (rs-232 / rs-485)
parameters input voltage, input current, output voltage, output current
ivr status power supply status, normal/ voltage regulation / bypass mode, output frequency, cooling system, system resume time, accumulated runtime, operation status, loading status, rs232 /rs485 / gprs
working mode 24hours / 7days long time full load continuous operation
warranty 2 years from delivery against manufacturing defects, material defects and workmanship fails.
bid submission documents
the bid submitted by the bidders shall include the following:
copy of trade license;
a valid copy of the tax clearance certificate;
price quotation with the delivery period
proof of previous similar works
well, prepared bids must be sent to ktrn not later than august 28, 2020 time: 11:00 am via email on
[email protected]late bids shall be rejected.
for any i formation please contact us on
[email protected]done at kigali, on 20th august 20, 2020
mike bwatete