Quotation are invited for Upgrade of Old Power Quality Monitoring System, Supply, Installation, Testing and Commissioning of Motor-VFD Temperature Control Systems.
Upgrade Pqm 1032003883rfx Description.
Upgrade of old Power Quality Monitoring System, Supply, Installation, Testing and comissioning of Motor-VFD Temperature Control Systems, RunTime Maintenance, Overhauling Monitoring and Energy
ManagementSystems for 8 nos of Motors, MV Switchgears and LV Switchgears.Location: Hatta Pumping Station Phase 1
BOQ, SCOPE AND REQUIREMENTS SERVICES
REQUIRED(1 OF 4 SERVICES LINES) REMOVE OLD
PQMS REPLACE WITH NEW CLASS A CERTIFIED
POWER QUAL
ITY METERS (PQM), UPGRADE, INTEGRATE,
SUPPLY, INSTALL, TEST AND COMMISSION
TOGETHER AS ONE SYSTEM WITH MOTOR-VFD
TEMPERATURE CONTROL
SYSTEM, REAL-TIME MOTOR MAINTENANCE
OVERHAULING MONITORING SYSTEM IN SERVICE
LINE ITEM 2 WITH ALL POWER QUALITY
MONITORING ACCESSOR
IES REQUIRED WITH ENERGY MANAGEMENT
SYSTEM IN HATTA PUMPING STATION PHASE 1-
UTILIZING THE LATEST CENTRAX CU3000 SYSTEM
CAPABILITY W
ITH THE FOLLOWING SPECIFIC FEATURES OF
CENTRAX CU3000 COMBINES IN ONE HOUSING FOR
PANEL MOUNTING THE FUNCTIONALITY OF A
HIGHLY ACCUR
ATE MEASUREMENT DEVICE FOR POWER
APPLICATIONS WITH FREELY PROGRAMMABLE PLC
WITH NO SEPARATE PLC REQUIRED, WITH AUTOMATED CONTROL SYS
TEM, A REMOTE DISPLAY OR AN ADDITIONAL DATA
COLLECTOR. SHALL BE DESIGNED AS FLEXIBLE
MEASUREMENT TECHNOLOGY, FOR POWER
QUALITY ANAL
YSIS, FOR ENERGY DATA MANAGEMENT AS WELL
FOR DATA AUTOMATION, INCLUDING
VISUALIZATION ON THE SPECIFIC PUMPING
STATION THAT WILL BE C
ENTRALIZED/ INTEGRATED IN FUTURE FOR
MULTIPLE PUMPING STATIONS SELECTED WITH
READY COMMUNICATIONS TO TRANSMIT AND
RECEIVED DATA FROM
A REMOTE CENTRALIZED STATION. THE DESIGN
INCLUDES VISUALIZATION POSSIBILITIES IN EACH
PUMPING STATION AS WELL ONE CENTRALIZED
CONTR
OL ROOM. APPLICATION INCLUDES FOR POWER
QUALITY MONITORING, INCLUDING ENERGY AND
LOAD MANAGEMENT FOR PQ3000 SYSTEM AND
AM3000. INCL
UDES ALL INSTALLATION, MECHANICAL
MODIFICATIONS OF MOUNTING IN EXISTING PANELS, ALL INSTRUMENTS MOUNTING, CABLES,
LUGS, CTS REQUIRED
, VTS, COMMUNICATIONS AND ITS COMMISSIONING
IN THE 3.3KV MEDIUM VOLTAGE SYSTEM AND LOW
VOLTAGE EQUIPMENT AT SITE. LOCATION: HATTA
P
UMPING STATION PHASE 1 POWER QUALITY
METER INSTRUMENT (PQMI)- QTY: 6 SETS (2 DT MV
MAINS); (1 GENERATOR MV MAINS) FOR EACH
STREAM A
& STREAM B - POWER MONITORING UNIT FOR LV
PANEL(MODEL SINEAX AM3000) THESE PQMS
SHALL BE CONNECTED/ COMMUNICATED IN ONE
SYSTEM TO
INTEGRATE WITH: - RACK MOUNTED SERVER WITH
LATEST WINDOWS SOFTWARE WITH CYBER
SECURITY PROTECTION, WITH MONITOR,
KEYBOARD AND MOUSE
. - SYSTEM STANDALONE WORKSTATION - POWER
MONITORING & CONTROL INSTRUMENT (PMCI):
QTY: 8 SETS (4 SETS FOR A-STREAM MOTOR &
ALLEN BRA
DLEY PF7000 CLASSIC MV VFD); (4 SETS FOR A-STREAM MOTOR & ALLEN BRADLEY PF7000
CLASSIC MV VFD) WITH RELATED SENSORS, CTS
AND ACCESSO
RIES AND ALL OTHER RELATED ACCESSORIES,
ENGINEERING TO COMPLETE THE INSTALLATION
AND REQUIREMENTS. POWER QUALITY METERS
SHALL HAVE
THE FOLLOWING REQUIREMENTS: POWER
QUALITY METER INSTRUMENT (PQMI): SHALL BE
CLASS A CERTIFIED MULTIFUNCTIONAL POWER
QUALITY MONITOR
(PQI) FOR MEASUREMENT, MONITORING AND
POWER QUALITY ANALYSIS IN PUMPING
STATION#S POWER SYSTEMS, ON-SITE EVENT
DISPLAY, TYPE SHALL
BE LINAX PQ3000, METROLOGICALLY CERTIFIED
24/7 POWER QUALITY MONITORING DEVICE OF
CLASS A ACC. IEC 61000#4#30 ED. 3. CAPABLE OF
GRAP
HING TRENDS UP TO 1/4 OF A CYCLE MINIMUM #
APPROX. 5 MILLISECONDS IN SINE WAVE GRAPH.
POWER QUALITY METER SHALL BE DIRECT
MEASUREMENT UP TO 690V, CATIII, EN50160 CONFORMITY
REPORTS. CONTRACTOR SHALL PROVIDE
CERTIFIED POWER QUALITY ANALYSIS, CLASS A
ACC. IEC 61000-
4-30 ED. 3 AND DOCUMENTED TESTING
CERTIFICATION OF ALL POWER QUALITY METER
FROM DULY AUTHORIZED WORLDWIDE KNOWN
CERTIFICATION COMPAN
Y. INSTRUMENT SHALL BE ABLE TO PROVIDE
EN50160 CONFORMITY REPORTS. INCLUDING ALL
CTS VTS CONNECTIONS, WIRINGS,
COMMUNICATIONS, ENGIN
EERING. SOFTWARES AND ACCESSORIES TO
COMPLETE THE INSTALLATION. PQMI SHALL BE
EQUIPPED WITH ENERGY MANAGEMENT
SOFTWARE, COMMUNICATI
ONS SYSTEMS TO BE INTEGRATED WITH CU3000
EMS@VFDS, PMUS AND STANDALONE
WORKSTATION WITH SERVER. QTY: 6 SETS (2 DT
MV MAINS); (1 GEN
ERATOR MV MAINS) FOR STREAM A & STREAM B
INSTRUMENTS SHALL STORE THE ACQUIRED
POWER QUALITY DATA IN THE STANDARDIZED POWER QUALITY
DATA INTERCHANGE FORMAT (PQDIF) ACCORDING
TO IEEE 1159.3. USING THE SMARTCOLLECT PM20
SOFTWARE OR EQUIVALENT, THE CONTENT OF
THESE F
ILES CAN BE DISPLAYED, STORED IN A DATABASE
AND ANALYZED. SHALL COMPLY TO THE
REFERENCE STANDARDS HIGHLIGHTED BELOW.
SMARTCOLLECT SO
FTWARE LICENSE SHALL BE LIFETIME. NOTE:
ABOVE IS PART OF THE EMS/ CONTROL SYSTEM
SPECS, FULL SPECIFICATIONS IS ATTACHED IN PR
AND S
HALL BE DOWNLOADED / COLLECTED FOR
CONTRACTOR TO COMPLY. PLEASE DOWNLOAD/
COLLECT THE FULL SPECIFICATIONS ATTACHED IN
THIS PR. C
ONTRACTOR SHALL COMPLY TO THE
SPECIFICATIONS DOWNLOADED AND SHALL
SUBMIT COMPLIANCE STATEMENT PER EACH
CLAUSE WITH SIGNATURE AND COM
PANY STAMP. COLLECT THE NON-DISCLOSURE
NDA AGREEMENT AND AFFIX SIGNATURE AND COMPANY STAMP FOR COMPLIANCE AND PRIOR
TO TECHNICAL DIS
CUSSION/ OFFER. CONTRACTOR SHALL COMPLY
TO SPECIFICATION AND REQUIREMENTS
ATTACHED IN THIS PR FOR FURTHER TECHNICAL
CLARIFICATIONS
, PLEASE CONTACT TO: LEONITO DE LOS SANTOS;
EMAIL:
[email protected]MOBILE: +971 527038780
2 ITEM-00001 BOQ, SCOPE AND REQUIREMENTS SERVICES
REQUIRED: (2 OF 4 INTERRELATED SERVICES)
PQM-EMS WITH MOTOR-VFD TEMPERATURE,
MOTOR MAINTENANC
E MONITORING SYSTEM WITH EMS SYSTEM
REMOVE OLD CONTROLS SYSTEM/ PQMS REPLACE
WITH NEW CLASS A CERTIFIED PQM - CU3000,
UPGRADE, REDE
SIGN, SUPPLY, INSTALLATION, TESTING AND
COMMISSIONING OF MOTOR-VFD TEMPERATURE
CONTROL SYSTEM, REAL-TIME MOTOR
MAINTENANCE OVERHAULI
NG MONITORING SYSTEM, CU3000 UTILIZING THE
LATEST CENTRAX CU3000 SYSTEM CAPABILITY WITH THE FOLLOWING SPECIFIC FEATURES OF
CENTRAX C
U3000 COMBINES IN ONE HOUSING FOR PANEL
MOUNTING THE FUNCTIONALITY OF A HIGHLY
ACCURATE MEASUREMENT DEVICE FOR POWER
APPLICATIONS WI
TH THE POSSIBILITIES OF A FREELY
PROGRAMMABLE PLC WITH NO SEPARATE PLC
REQUIRED, HAVING AUTOMATED CONTROL
SYSTEM, A REMOTE DISPLAY O
R AN ADDITIONAL DATA COLLECTOR. EQUIPPED
WITH MEASUREMENT TECHNOLOGY FOR POWER
QUALITY ANALYSIS @ VFD LOADS, FOR ENERGY
DATA MANAGE
MENT AS WELL FOR DATA AUTOMATION,
INCLUDING VISUALIZATION ON THE SPECIFIC
PUMPING STATION AND CAN BE CENTRALIZED IN
MULTIPLE PUMPING
STATIONS SELECTED WITH READY
COMMUNICATIONS TO TRANSMIT AND RECEIVED
DATA FROM A REMOTE CENTRALIZED STATION.
THE DESIGN INCLUDES VI
SUALIZATION POSSIBILITIES IN EACH PUMPING
STANDARD TERMS & CONDITIONS
1) Prices should be `DDP` delivery duty paid at DEWA stores.
2) Quotation to be submitted only in local currency U.A.E Dirhams
3) DEWA Standard payment terms is `30 days credit` from the date of acceptance of material
4) No DEWA staff or his or her relatives up to third degree should have ownership or partnership in your company, and your participation in DEWA tenders / RFQs should not constitute a Conflict or perceived Conflict of Interest.