Expired Tender UAE ICB TOT Ref. 50481846

Upgrade of Old Power Quality Monitoring System Tender - 50481846

Tender notice from UAE, published on 22 Feb 2021.

Executive Summary

The DUBAI ELECTRICITY & WATER AUTHORITY (DEWA) has issued a Tender notice for the procurement of a Upgrade of Old Power Quality Monitoring System, Supply, Installation, Testing and Commissioning of Motor-VFD Temperature Control Systems in the UAE. This Tender notice was published on 22 Feb 2021 and is scheduled to close on 28 Feb 2021, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 50481846, while the tender notice number is 2332100217 and Register on the platform.

Key facts

Summary
Upgrade of Old Power Quality Monitoring System, Supply, Installation, Testing and Commissioning of Motor-VFD Temperature Control Systems
TOT Ref. No.
50481846
Document Ref. No.
2332100217
Country
UAE
Notice type
Tender
Competition
ICB
Publication date
22 Feb 2021
Bid deadline
28 Feb 2021
EMD
Refer Document
Tender value
Refer Document
Purchaser ownership
-
Financier
Self Financed

Purchaser details

Purchaser contact is for registered users

Login to see details

Tender details

Quotation are invited for Upgrade of Old Power Quality Monitoring System, Supply, Installation, Testing and Commissioning of Motor-VFD Temperature Control Systems.
Upgrade Pqm 1032003883rfx Description.
Upgrade of old Power Quality Monitoring System, Supply, Installation, Testing and comissioning of Motor-VFD Temperature Control Systems, RunTime Maintenance, Overhauling Monitoring and Energy

ManagementSystems for 8 nos of Motors, MV Switchgears and LV Switchgears.Location: Hatta Pumping Station Phase 1
BOQ, SCOPE AND REQUIREMENTS SERVICES

REQUIRED(1 OF 4 SERVICES LINES) REMOVE OLD

PQMS REPLACE WITH NEW CLASS A CERTIFIED

POWER QUAL

ITY METERS (PQM), UPGRADE, INTEGRATE,

SUPPLY, INSTALL, TEST AND COMMISSION

TOGETHER AS ONE SYSTEM WITH MOTOR-VFD

TEMPERATURE CONTROL

SYSTEM, REAL-TIME MOTOR MAINTENANCE

OVERHAULING MONITORING SYSTEM IN SERVICE

LINE ITEM 2 WITH ALL POWER QUALITY

MONITORING ACCESSOR

IES REQUIRED WITH ENERGY MANAGEMENT

SYSTEM IN HATTA PUMPING STATION PHASE 1-

UTILIZING THE LATEST CENTRAX CU3000 SYSTEM

CAPABILITY W

ITH THE FOLLOWING SPECIFIC FEATURES OF

CENTRAX CU3000 COMBINES IN ONE HOUSING FOR

PANEL MOUNTING THE FUNCTIONALITY OF A

HIGHLY ACCUR

ATE MEASUREMENT DEVICE FOR POWER

APPLICATIONS WITH FREELY PROGRAMMABLE PLC

WITH NO SEPARATE PLC REQUIRED, WITH AUTOMATED CONTROL SYS

TEM, A REMOTE DISPLAY OR AN ADDITIONAL DATA

COLLECTOR. SHALL BE DESIGNED AS FLEXIBLE

MEASUREMENT TECHNOLOGY, FOR POWER

QUALITY ANAL

YSIS, FOR ENERGY DATA MANAGEMENT AS WELL

FOR DATA AUTOMATION, INCLUDING

VISUALIZATION ON THE SPECIFIC PUMPING

STATION THAT WILL BE C

ENTRALIZED/ INTEGRATED IN FUTURE FOR

MULTIPLE PUMPING STATIONS SELECTED WITH

READY COMMUNICATIONS TO TRANSMIT AND

RECEIVED DATA FROM

A REMOTE CENTRALIZED STATION. THE DESIGN

INCLUDES VISUALIZATION POSSIBILITIES IN EACH

PUMPING STATION AS WELL ONE CENTRALIZED

CONTR

OL ROOM. APPLICATION INCLUDES FOR POWER

QUALITY MONITORING, INCLUDING ENERGY AND

LOAD MANAGEMENT FOR PQ3000 SYSTEM AND

AM3000. INCL

UDES ALL INSTALLATION, MECHANICAL

MODIFICATIONS OF MOUNTING IN EXISTING PANELS, ALL INSTRUMENTS MOUNTING, CABLES,

LUGS, CTS REQUIRED

, VTS, COMMUNICATIONS AND ITS COMMISSIONING

IN THE 3.3KV MEDIUM VOLTAGE SYSTEM AND LOW

VOLTAGE EQUIPMENT AT SITE. LOCATION: HATTA

P

UMPING STATION PHASE 1 POWER QUALITY

METER INSTRUMENT (PQMI)- QTY: 6 SETS (2 DT MV

MAINS); (1 GENERATOR MV MAINS) FOR EACH

STREAM A

& STREAM B - POWER MONITORING UNIT FOR LV

PANEL(MODEL SINEAX AM3000) THESE PQMS

SHALL BE CONNECTED/ COMMUNICATED IN ONE

SYSTEM TO

INTEGRATE WITH: - RACK MOUNTED SERVER WITH

LATEST WINDOWS SOFTWARE WITH CYBER

SECURITY PROTECTION, WITH MONITOR,

KEYBOARD AND MOUSE

. - SYSTEM STANDALONE WORKSTATION - POWER

MONITORING & CONTROL INSTRUMENT (PMCI):

QTY: 8 SETS (4 SETS FOR A-STREAM MOTOR &

ALLEN BRA

DLEY PF7000 CLASSIC MV VFD); (4 SETS FOR A-STREAM MOTOR & ALLEN BRADLEY PF7000

CLASSIC MV VFD) WITH RELATED SENSORS, CTS

AND ACCESSO

RIES AND ALL OTHER RELATED ACCESSORIES,

ENGINEERING TO COMPLETE THE INSTALLATION

AND REQUIREMENTS. POWER QUALITY METERS

SHALL HAVE

THE FOLLOWING REQUIREMENTS: POWER

QUALITY METER INSTRUMENT (PQMI): SHALL BE

CLASS A CERTIFIED MULTIFUNCTIONAL POWER

QUALITY MONITOR

(PQI) FOR MEASUREMENT, MONITORING AND

POWER QUALITY ANALYSIS IN PUMPING

STATION#S POWER SYSTEMS, ON-SITE EVENT

DISPLAY, TYPE SHALL

BE LINAX PQ3000, METROLOGICALLY CERTIFIED

24/7 POWER QUALITY MONITORING DEVICE OF

CLASS A ACC. IEC 61000#4#30 ED. 3. CAPABLE OF

GRAP

HING TRENDS UP TO 1/4 OF A CYCLE MINIMUM #

APPROX. 5 MILLISECONDS IN SINE WAVE GRAPH.

POWER QUALITY METER SHALL BE DIRECT

MEASUREMENT UP TO 690V, CATIII, EN50160 CONFORMITY

REPORTS. CONTRACTOR SHALL PROVIDE

CERTIFIED POWER QUALITY ANALYSIS, CLASS A

ACC. IEC 61000-

4-30 ED. 3 AND DOCUMENTED TESTING

CERTIFICATION OF ALL POWER QUALITY METER

FROM DULY AUTHORIZED WORLDWIDE KNOWN

CERTIFICATION COMPAN

Y. INSTRUMENT SHALL BE ABLE TO PROVIDE

EN50160 CONFORMITY REPORTS. INCLUDING ALL

CTS VTS CONNECTIONS, WIRINGS,

COMMUNICATIONS, ENGIN

EERING. SOFTWARES AND ACCESSORIES TO

COMPLETE THE INSTALLATION. PQMI SHALL BE

EQUIPPED WITH ENERGY MANAGEMENT

SOFTWARE, COMMUNICATI

ONS SYSTEMS TO BE INTEGRATED WITH CU3000

EMS@VFDS, PMUS AND STANDALONE

WORKSTATION WITH SERVER. QTY: 6 SETS (2 DT

MV MAINS); (1 GEN

ERATOR MV MAINS) FOR STREAM A & STREAM B

INSTRUMENTS SHALL STORE THE ACQUIRED

POWER QUALITY DATA IN THE STANDARDIZED POWER QUALITY

DATA INTERCHANGE FORMAT (PQDIF) ACCORDING

TO IEEE 1159.3. USING THE SMARTCOLLECT PM20

SOFTWARE OR EQUIVALENT, THE CONTENT OF

THESE F

ILES CAN BE DISPLAYED, STORED IN A DATABASE

AND ANALYZED. SHALL COMPLY TO THE

REFERENCE STANDARDS HIGHLIGHTED BELOW.

SMARTCOLLECT SO

FTWARE LICENSE SHALL BE LIFETIME. NOTE:

ABOVE IS PART OF THE EMS/ CONTROL SYSTEM

SPECS, FULL SPECIFICATIONS IS ATTACHED IN PR

AND S

HALL BE DOWNLOADED / COLLECTED FOR

CONTRACTOR TO COMPLY. PLEASE DOWNLOAD/

COLLECT THE FULL SPECIFICATIONS ATTACHED IN

THIS PR. C

ONTRACTOR SHALL COMPLY TO THE

SPECIFICATIONS DOWNLOADED AND SHALL

SUBMIT COMPLIANCE STATEMENT PER EACH

CLAUSE WITH SIGNATURE AND COM

PANY STAMP. COLLECT THE NON-DISCLOSURE

NDA AGREEMENT AND AFFIX SIGNATURE AND COMPANY STAMP FOR COMPLIANCE AND PRIOR

TO TECHNICAL DIS

CUSSION/ OFFER. CONTRACTOR SHALL COMPLY

TO SPECIFICATION AND REQUIREMENTS

ATTACHED IN THIS PR FOR FURTHER TECHNICAL

CLARIFICATIONS

, PLEASE CONTACT TO: LEONITO DE LOS SANTOS;

EMAIL: [email protected]

MOBILE: +971 527038780

2 ITEM-00001 BOQ, SCOPE AND REQUIREMENTS SERVICES

REQUIRED: (2 OF 4 INTERRELATED SERVICES)

PQM-EMS WITH MOTOR-VFD TEMPERATURE,

MOTOR MAINTENANC

E MONITORING SYSTEM WITH EMS SYSTEM

REMOVE OLD CONTROLS SYSTEM/ PQMS REPLACE

WITH NEW CLASS A CERTIFIED PQM - CU3000,

UPGRADE, REDE

SIGN, SUPPLY, INSTALLATION, TESTING AND

COMMISSIONING OF MOTOR-VFD TEMPERATURE

CONTROL SYSTEM, REAL-TIME MOTOR

MAINTENANCE OVERHAULI

NG MONITORING SYSTEM, CU3000 UTILIZING THE

LATEST CENTRAX CU3000 SYSTEM CAPABILITY WITH THE FOLLOWING SPECIFIC FEATURES OF

CENTRAX C

U3000 COMBINES IN ONE HOUSING FOR PANEL

MOUNTING THE FUNCTIONALITY OF A HIGHLY

ACCURATE MEASUREMENT DEVICE FOR POWER

APPLICATIONS WI

TH THE POSSIBILITIES OF A FREELY

PROGRAMMABLE PLC WITH NO SEPARATE PLC

REQUIRED, HAVING AUTOMATED CONTROL

SYSTEM, A REMOTE DISPLAY O

R AN ADDITIONAL DATA COLLECTOR. EQUIPPED

WITH MEASUREMENT TECHNOLOGY FOR POWER

QUALITY ANALYSIS @ VFD LOADS, FOR ENERGY

DATA MANAGE

MENT AS WELL FOR DATA AUTOMATION,

INCLUDING VISUALIZATION ON THE SPECIFIC

PUMPING STATION AND CAN BE CENTRALIZED IN

MULTIPLE PUMPING

STATIONS SELECTED WITH READY

COMMUNICATIONS TO TRANSMIT AND RECEIVED

DATA FROM A REMOTE CENTRALIZED STATION.

THE DESIGN INCLUDES VI

SUALIZATION POSSIBILITIES IN EACH PUMPING
STANDARD TERMS & CONDITIONS

1) Prices should be `DDP` delivery duty paid at DEWA stores.

2) Quotation to be submitted only in local currency U.A.E Dirhams

3) DEWA Standard payment terms is `30 days credit` from the date of acceptance of material

4) No DEWA staff or his or her relatives up to third degree should have ownership or partnership in your company, and your participation in DEWA tenders / RFQs should not constitute a Conflict or perceived Conflict of Interest.

Documents

Tender Notice
Login to view

UAE Public Procurement Intelligence

Frequently asked questions

The bid deadline for Upgrade of Old Power Quality Monitoring System, Supply, Installation, Testing and Commissioning of Motor-VFD Temperature Control Systems was 28 Feb 2021. Bidding is closed.

This tender has been issued by DUBAI ELECTRICITY & WATER AUTHORITY (DEWA) in UAE.

The tender value is not disclosed; please refer to the tender document. EMD / bid security details are provided in the tender document.

This tender is Self Financed

The tender notice and related documents are listed in the Documents section above. Select a document to view or download it. Please log in or register to access the documents. If you cannot find additional documents in the Documents section, please log in to your account and Send Document Request from your account section.

The TendersOnTime reference is 50481846. The purchaser document reference is 2332100217.

Browse other tenders from UAE or search by relevant keywords and CPV classification.