The HOSPITAL AUTHORITY (HA) has issued a Tender notice for the procurement of a Supply and Installation of Power Supply, Uninterruptable for New Block Redevelopment Projects of Queen Man- Hospital and Cranlham Hospital in the Hong Kong. This Tender notice was published on 22 Oct 2022 and is scheduled to close on 16 Nov 2022, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 73496091, while the tender notice number is HKWC-T012/21(P-HKWC) and Register on the platform.

Key facts

Summary
Supply and Installation of Power Supply, Uninterruptable for New Block Redevelopment Projects of Queen Man- Hospital and Cranlham Hospital
TOT Ref. No.
73496091
Document Ref. No.
HKWC-T012/21(P-HKWC)
Country
Hong Kong
Notice type
Tender
Competition
ICB
Publication date
22 Oct 2022
Bid deadline
16 Nov 2022
EMD
Refer Document
Tender value
Refer Document
Purchaser ownership
Public
Financier
Self Financed

Purchaser details

Purchaser contact is for registered users

Login to see details

Tender details

Tenders are invited for Supply and Installation of Power Supply, Uninterruptable for New Block Redevelopment Projects of Queen Man- Hospital and Cranlham Hospital, Hong Kong West Cluster, Hospital Authority.
1 Introduction

1.1 The tender calls for the supply, delivery and installation, and

Testing and Commissioning for four (4) complete sets of

Uninterruptible Power Supply (UPS), Isolation Transformer,

Battery c/w Battery Monitoring System for Hospital Authority.

- 2 complete sets for Queen Mary Hospital

- 2 complete sets for Grantham Hospital

M

Part A Equipment Specification

2 General Description

2.1 Four (4) complete sets of Uninterruptible Power Supply (UPS)

shall include:

M

2.1.1 Uninterruptible Power Supply: 4 sets of online double

conversion modular UPS.

M

2.1.2 Isolation Transformer: 4 sets M

2.1.3 Battery completed with Battery Monitoring System: 4 sets M

2.1.4 Electrical and Others:

 External Make-Before-Break Maintenance Bypass Panel

(EMBP): 4 sets

M

3 Specification for Uninterruptible Power Supply (UPS)

(Refer to Clause 2.1.1)

Each set of UPS shall have the following features:

M

3.1 Design

3.1.1 The UPS shall be designed and operated in Modular

Redundancy Architecture. It shall be made up of one or more

physically detachable equipment modules or cabinets, of drawout type and removable from the front of the UPS system.

Tenderers shall provide relevant information / specify the

requirements for equipment on offer in EOI return for

M

consideration. The Indicative UPS Schematic Diagram Drawing

would be provided in tender stage.

3.1.2 The UPS shall be dual feed input. M

3.1.3 The UPS shall be supplied with enough power module so that it

can support design load of following power rating in N+1

redundancy.

QMH: 140kW

GH: 200kW

M

3.1.4 Input Power Factor 0.99

Output Power Factor = 1

M

3.1.5 The control module and all power modules of the UPS Unit shall

be housed in single equipment rack.

M

3.1.6 Expandability:

In case future power expansion is needed, UPS Frame of

additional (minimum following power rating per frame and up

to 4 frames) shall be able to install to expand the UPS power

rating without power interruption to supporting load.

QMH: 140kW

GH: 200kW

M

3.1.7 Any installation or system reconfiguration required for the

expansion shall not affect the live operations of the modular

UPS. There is required to put the UPS onto bypass mode for

expansion.

M

3.1.8 The overall size of the UPS frame should not be larger than

900*2100*1200 (W*H*D in mm) per frame in all directions

M

3.1.9 The availability of the system shall not be less than 99.9995%. M

3.1.10 The current rating of the inter-battery cables shall be greater than

1.5x of the nominal maximum of charge / discharge current.

M

3.1.11 The rectifier / charger unit shall be provided with an input

isolating switch / circuit breaker.

The rectifier / charger unit shall have protection to prevent the

battery from over-charging due to battery charger / rectifier

fault. An adjustable battery current limiting device shall limit

the battery recharge current to the maximum value

recommended by the battery manufacturer.

M

The rectifier / charger unit shall be able to automatically adjust

the battery float charge voltage based on temperature variation

in accordance with battery manufacturer-s recommendation.

The charging current shall be adjustable from 5% to 30% so as

to limit the total input current when the battery has been

discharged.

3.2 Power Module:

3.2.1 Power Rating:

≥ 25kW per power module

The power modules shall be hot-swappable such that

replacement of the faulty modules can be carried out on-line

without any output interruption.

M

3.2.2 Features:

3.2.2.1 Soft Start and with Internal Backfeed Protection. M

3.2.2.2 UPS efficiency in double conversion mode ≥ 97% and shall be

able to maximize to 99% with energy save mode. (Self-declare

is not accepted, Manufacturer written literature with supporting

data required)

M

3.2.3 Input Voltage:

Three-phase 380V+N 50/60Hz

M

3.2.4 Input Voltage Range (V): 340 - 437 or wider M

3.2.5 Input Frequency : 40 to 70 Hz or wider M

3.2.6 Output Voltage:

Three-phase 380V+N 50/60Hz

M

3.2.7 Total voltage harmonic distortion: M

3.2.7.1 ≤ 1% (100% linear load) M

3.2.7.2 ≤ 5% (100% non-linear load) M

3.2.8 Overload on inverter: M

3.2.8.1 1 min from 125% M

3.2.8.2 10 seconds from 150% M

3.2.9 Permitted load power factor: 0.8 lagging to 0.8 leading M

3.2.10 Efficiency in double conversion On-Line mode ≥ 97%

Efficiency in Energy Saver Mode maximize to 99%

M

3.2.11 Energy efficiency of the UPS system shall not be less than 92%

at 50% rated load.

M

3.3 Internal Static Bypass Switch (SBP)

3.3.1 A full rating internal SBP shall be equipped for the UPS M

3.3.2 The SBP module shall be hot swappable M

3.3.3 The SBP shall be fuse and back feed protected M

3.3.4 Overload on bypass: M

3.3.4.1 110% continuous M

3.3.4.2 1000% 20 milliseconds M

3.4 UPS centralized communication module (UCM)

3.4.1 The UCM shall be hot swappable M

3.5 Battery Connection:

3.5.1 The UPS shall be ready for connecting to VRLA or Li-ion

Battery without any hardware modification nor additional cost.

M

3.6 Connectivity

3.6.1 Each UPS system shall equip with Simple Network

Management Protocol (SNMP v1 or v2) network adaptor for

remote monitoring through Ethernet network.

M

3.6.2 The UPS shall support TCP/IP and SNMP traps protocols for

remote monitoring. The network interface shall be Ethernet

10/100 Base T standard with RJ45 jack.

M

3.6.3 Each UPS system shall equip with: M

3.6.3.1 Mini-slot ports for optional cards M

3.6.3.2 Device USB and/or Host USB M

3.6.3.3 RS-232/RS-485/USB service port M

3.6.3.4 Relay output M

3.6.3.5 Output terminal/ connection for dummy load test (full load) and

battery discharge test

M

3.6.3.6 Building alarm inputs M

3.6.3.7 Emergency Power-Off (EPO) button status M

3.6.4 UPS system shall provide interfacing connections (e.g. SNMP,

Modbus, BACnet) to Central Control and Monitoring System

(CCMS), including but not be limited to:

- UPS status (on/off/fault)

- Static bypass status

- Internal static transfer switch status (not applicable to the UPS

for GH)

- Common fault alarm

- Input voltage(s)

- Input current(s)

- Input frequency

- Input power

- Output voltage(s)

- Output current(s)

- Output frequency

- Output power

- Output load rate (%) (not applicable to the UPS for GH)

- Bypass voltage (not applicable to the UPS for GH)

- Bypass current (not applicable to the UPS for GH)

- Battery voltage

- Battery temperature

- UPS input power supply failure

- UPS system failure

- Battery system failure

The tenderer shall be fully responsible for liaison and

coordination works with relevant parties including the Main

Contractor and other Mechanical and Electrical (M&E)

contractors for exact requirements and interfacing arrangement.

M

3.7 Standard Compliance

Equipment offered shall comply with:

M

3.7.1 Latest version of General Technical Specification for

Uninterruptible Power Supply (UPS), issued by Electrical and

Mechanical Services Department (EMSD)

M

3.7.2 Safety certification: IEC 62040-1 M

3.7.3 Electromagnetic compatibility (EMC) certification:

IEC 62040-2

M

3.7.4 Performance certification: IEC 62040-3 M Etc.

Documents

Tender Notice
Login to view

Hong Kong Public Procurement Intelligence

Frequently asked questions

The bid deadline for Supply and Installation of Power Supply, Uninterruptable for New Block Redevelopment Projects of Queen Man- Hospital and Cranlham Hospital was 16 Nov 2022. Bidding is closed.

This tender has been issued by HOSPITAL AUTHORITY (HA) in Hong Kong.

The tender value is not disclosed; please refer to the tender document. EMD / bid security details are provided in the tender document.

This tender is Self Financed

The tender notice and related documents are listed in the Documents section above. Select a document to view or download it. Please log in or register to access the documents. If you cannot find additional documents in the Documents section, please log in to your account and Send Document Request from your account section.

The TendersOnTime reference is 73496091. The purchaser document reference is HKWC-T012/21(P-HKWC).

Browse other tenders from Hong Kong or search by relevant keywords and CPV classification.