Maintenance of Fire Water Tank Tender in UAE - 50764566

Tender notice from UAE, published on 02 Mar 2021.

Executive Summary

The DUBAI ELECTRICITY & WATER AUTHORITY (DEWA) has issued a Tender notice for the procurement of a Maintenance of Fire Water Tank in the UAE. This Tender notice was published on 02 Mar 2021 and is scheduled to close on 04 Mar 2021, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 50764566, while the tender notice number is 2412100236 and Register on the platform.

Key facts

Summary
Maintenance of Fire Water Tank
TOT Ref. No.
50764566
Document Ref. No.
2412100236
Country
UAE
Notice type
Tender
Competition
ICB
Publication date
02 Mar 2021
Bid deadline
04 Mar 2021
EMD
Refer Document
Tender value
Refer Document
Purchaser ownership
-
Financier
Self Financed

Purchaser details

Purchaser contact is for registered users

Login to see details

Tender details

Quotation are invited for Maintenance of Fire Water Tank.
Water Tank 1032004082rfx Description
1 ITEM-00001 B) MAINTENACE OF FIRE WATER TANK DURING 10

YEAR WARRANTY PERIOD SCOPE OF WORK: ·#OEM

RECOMMENDED MAINTENANCE SCHEDULE AND

FREQUENCY

TO BE FOLLOWED FOR INTERNAL INSPECTION.

·#CONTRACTOR SHALL GIVE DEWA MINIMUM 2

MONTH#S PRIOR INTIMATION FOR SCHEDULING

MAINTENANCE A

CTIVITIES. ·#ALL TOOLS AND ASSOCIATED

ACTIVITIES RELATED TO MAINTENANCE SCHEDULE

SHALL BE CONTRACTOR RESPONSIBILITY.

·#CONTRACTOR TO

FOLLOW DEWA OUTAGE AND SAFETY

PROCEDURES ALWAYS.

1 G01

2 ITEM-00001 A) REPLACEMENT OF FIREWATER TANK -2 IN

QUSAIS EAST (QSSE) 132KV SUBSTATION SCOPE

OF WORK O#REMOVAL OF EXISTING FIRE WATER

TANK. O#D

ISPOSAL OF THE REMOVED TANK TO DEWA

CENTRAL STORE OR SCRAP YARD. O#SUPPLY,

INSTALLATION, TESTING AND COMMISSIONING OF

FIRE WATER TAN

K AS PER DEWA-TP SPECIFICATION. O#EXISTING

1 G01

TANK CAPACITY IS 172 M3 AND DIMENSION: 5.35 M

DIA X 8.48 M HT O#ONLY LATEST DEWA-TP APPR

OVED FIRE WATER TANKS SHALL BE ACCEPTED.

O#MODIFICATION/RECTIFICATION OF FOUNDATION,

PIPING AND SUPPORTS AS REQUIRED. O#ALL

ASSOCIAT

ED CIVIL, ELECTRICAL AND MECHANICAL WORKS

AS PER SITE REQUIREMENTS. PRODUCT DETAILS

·#THE CAPACITY OF THE FIRE WATER TANK SHALL

BE

SIMILAR AS EXISTING ONE. ·#NEW TANK SHALL BE

INTER-CONNECTED WITH SUITABLE PIPING/VALVE

ARRANGEMENTS TO FACILITATE ISOLATION FOR

THE

PURPOSE OF MAINTENANCE/REPAIRS. ·#THE TANK

SHALL BE ANY OF THE FOLLOWING: A.#POWDER

COATED ALUMINIUM WITH EPDM LINER

B.#POWDER COAT

ED GALVANIZED IRON (GI) WITH EPDM LINER ·#ALL

PIPES, METALLIC PARTS AND EQUIPMENT IN

CONTACT WITH WATER IS TO BE OF STAINLESS

STEEL

316L. ·#THE TANK SHALL INCLUDE THE FOLLOWING: A.#EXTERNAL CAT LADDER SHALL BE

STAINLESS STEEL/ ALUMINUM WITH INTERMEDIATE

PLATFORM F

OR THE ACCESS OF MANHOLE AND INSPECTION

OF FLOAT VALVE CHAMBER. B.#THE SUCTION,

DRAIN, WATER CONTENT GAUGE, OVERFLOW

FLANGE, TEST LI

NE, INFILLING LINE AND PRESSURE RELIEF LINE

CONNECTION. C.#HIGH LEVEL AND LOW LEVEL

FLOAT SWITCH (SHALL BE INTERFACED WITH THE

FIRE

ALARM SYSTEM BY INDIVIDUAL MODULE)

D.#MODULATING CONTROL FLOAT VALVE BALL

TYPE WITH STAINLESS STEEL BALL AND

STAINLESS STEEL PILOT P

IPING ACCESSORIES. E.#FIRE PUMP TEST RETURN

LINE NOZZLE (FLANGED) F.#WATER CONTENT DIAL

GAUGE, 150MM (6#) SHALL BE SUITABLE FOR OUTD

OOR APPLICATION AND UV PROTECTED, THE

GAUGE SHOULD READ BOTH WATER VOLUME AND

LEVEL. G.#FIRE PUMP SUCTION LINE NOZZLE

(FLANGED) H.#6

5 MM DRAIN OUTLET CONNECTION (FLANGED END GATE VALVE) I.#AIR VENT #TUBE VENT WITH

SS316L BIRD/ INSECT SCREEN J.#FIRE PUMP TEST

RETUR

N LINE IS TO BE CONNECTED TO BOTH THE TANKS,

EACH BRANCH SHALL BE PROVIDED WITH OS&Y

GATE VALVE. ·#THE FIREWATER TANKS SHALL

HAVE F

IRE PUMP SUCTION PIPE ARRANGEMENT WITH

SUMP AND VORTEX PLATE. ·#THE ALUMINIUM

TANKS / GI TANKS ROOF PURLIN AND SHEET SHALL

BE MORE R

IGID AND DURABLE TO HANDLE THE LOAD OF

PEOPLE DURING MAINTENANCE. ·#THE

ALUMINIUM/GI TANKS SHALL BE PROVIDED WITH

LOW LEVEL MANHOLE

(FROM SIDE) OF MINIMUM 600X600 MM TO ACCESS

THE TANK FROM GROUND INSTEAD OF FROM

ROOF. ·#THE FLOAT VALVE CHAMBER AND

MANHOLE ACCESS

SHALL BE SEPARATE TO HAVE EASY AND SAFE

ACCESS TO GO INTO THE TANKS. ·#THE TANKS

SHALL BE PROVIDED WITH FILLING CONNECTION

DIRECTLY FROM DEWA LINE WITH A FLOAT OPERATED VALVE

FOR AUTOMATIC REFILLING. ·#THE MODULATING

FLOAT VALVE SHALL BE MOUNTED AT GROUND

LEVEL. ·

#MANUFACTURER#S NAMEPLATE SHALL BE

PROVIDED WITH TANK SERIAL NUMBER, TANK

DIAMETER, HEIGHT, TYPE, MAXIMUM DESIGN

CAPACITY, YEAR OF M

ANUFACTURE AND OTHER PERTINENT DATA. ·#ALL

IDENTIFICATION TAGS/BOARD SHALL BE

ENGRAVED AND WEATHERPROOF. ·#CONTRACTOR

TO FOLLOW DEWA

OUTAGE AND SAFETY PROCEDURES ALWAYS.

·#DEWA NORMAL WORKING HOURS TO BE

CONSIDERED FOR SITE EXECUTION. ·#AS BUILT

DRAWINGS, TANK SHE

ET CALCULATIONS, OPERATION AND

MAINTENANCE MANUALS AND TEST REPORTS TO

BE PROVIDED. TANK WARRANTY: ·#RELIABILITY

RUN PERIOD OF 2

MONTHS AFTER TANK COMPLETION IS APPLICABLE

FOR TAKING OVER BY DEWA. ·#THE TANK

MANUFACTURER SHALL INCLUDE A 10-YEAR WARRANTY ON ALL

TANK MATERIALS AND WORKMANSHIP FOR A

SPECIFIED PERIOD. THE WARRANTY SHALL

PROVIDE ASSURANCE AGAINST DEFECTS IN

MATERIAL, COATINGS AN

D WORKMANSHIP OF MAIN TANK AND ASSOCIATED

FITTINGS FOR A PERIOD OF TEN (10) YEARS FOR

NEW TANKS. WARRANTY WILL BE CALCULATED

FROM TH

E DATE OF TAKING OVER BY DEWA. NOTE:

ARRANGING TANKER FOR DRAINING/ DEWATERING

OF FIREWATER TANK DURING LEAKAGE

RECTIFICATION UNDER

WARRANTY IS CONTRACTOR`S RESPONSIBILITY.

GENERAL CONDITION THE CONTRACTOR SHALL

SUBMIT TECHNICAL OFFER WITH FULL DETAILED

WORKING P

ROGRAM TO EXECUTE THIS JOB. THE

CONTRACTOR MUST COMPLETE THE EXECUTION

OF THE PROJECT WITHIN 6 MONTHS PERIOD. B)

MAINTENACE OF FIRE

WATER TANK DURING 10 YEAR WARRANTY

PERIOD SCOPE OF WORK: ·#OEM RECOMMENDED MAINTENANCE SCHEDULE AND FREQUENCY TO BE

FOLLOWED FOR IN

TERNAL INSPECTION. ·#CONTRACTOR SHALL GIVE

DEWA MINIMUM 2 MONTH#S PRIOR INTIMATION

FOR SCHEDULING MAINTENANCE ACTIVITIES. ·#ALL

TOOL

S AND ASSOCIATED ACTIVITIES RELATED TO

MAINTENANCE SCHEDULE SHALL BE CONTRACTOR

RESPONSIBILITY. ·#CONTRACTOR TO FOLLOW

DEWA OUTAGE A

ND SAFETY PROCEDURES ALWAYS. SITE VISIT

CAN BE ARRANGED ON ONLY ONE DAY FOR ALL

INTERESTED VENDORS. DEWA PTW PROCEDURE

TO BE FOLLOW

ED ALWAYS. FOR SITE VISIT AND PTW, CONTACT

ENGR. AARON 055-2651235 & ENGR. RAJAGOPAL

056-8980236 OTHER ENQUIRIES, CONTACT ENGR.

ANEE

Z 055-9660850
STANDARD TERMS & CONDITIONS

1) Prices should be `DDP` delivery duty paid at DEWA stores.

2) Quotation to be submitted only in local currency U.A.E Dirhams

3) DEWA Standard payment terms is `30 days credit` from the date of acceptance of material

4) No DEWA staff or his or her relatives up to third degree should have ownership or partnership in your company, and your participation in DEWA tenders / RFQs should not constitute a Conflict or perceived Conflict of Interest.

Documents

Tender Notice
Login to view

UAE Public Procurement Intelligence

Frequently asked questions

The bid deadline for Maintenance of Fire Water Tank was 04 Mar 2021. Bidding is closed.

This tender has been issued by DUBAI ELECTRICITY & WATER AUTHORITY (DEWA) in UAE.

The tender value is not disclosed; please refer to the tender document. EMD / bid security details are provided in the tender document.

This tender is Self Financed

The tender notice and related documents are listed in the Documents section above. Select a document to view or download it. Please log in or register to access the documents. If you cannot find additional documents in the Documents section, please log in to your account and Send Document Request from your account section.

The TendersOnTime reference is 50764566. The purchaser document reference is 2412100236.

Browse other tenders from UAE or search by relevant keywords and CPV classification.