Generators With Installation For Tumaco Narino, Colombia The Contractor developed plans and works shall comply with quote mark Norma Sismo Resistente quote mark (NSR) - 2010 code, Colombian codes quote mark Norma Tecnica Colombiana quote mark (NTC) - 1500, quote mark Reglamento T cnico del Sector de Agua Potable y Saneamiento B sico quote mark (RAS)-2000, NTC 2050 and RETIE. Designs shall include the electrical design and generator shack design. The Contractor shall verify that the value of the resistance is the required value of ( less than 25 ohms) or as required by code. The Contractor shall include a Lightning Protection System Study IAW NTC 4552. ARSOUTH acceptance of the drawings does not waive the contractor's responsibility to comply with the corresponding codes and rules for the design and construction. The contractor shall submit within 10 days with after contract award, the construction and electrical designs/drawings, and diagrams based on the codes, signed and certified by a licensed structural and electrical engineers. He shall provide electric load study results. The Contractor shall also provide electrical load calculations to substantiate a capacity increase of 20 percent. Formats for the drawings shall be submitted in AutoCad 2010 and pdf. The U.S. Army South engineer will approve the design. Neither the U.S. Government's review, approval or acceptance of, nor payment for the requirement required under this contract shall be construed to operate as a waiver of any rights under this contract or of any cause of actions arising out to the performance of this contract, and the Contractor shall be and remain liable to the U.S. Government in accordance with applicable law for all damages to the U.S. Government caused by the Contractor's negligent performance under this contract. The work will be executed based on the following requirements: The contractor shall be responsible for the professional quality, technical accuracy, and the coordination of designs, drawings, and specifications, furnished by the contractor under this contract. The contractor shall, without additional compensation, correct or revise any errors or deficiencies in its designs, drawings, and specifications to meet local and national codes and standards. Once the design is approved, any design changes will be submitted to U.S. Army South Engineer for approval. Contractor shall not proceed without prior approval of the U.S Army South Engineer. If the design changes imply cost to the government, the Contractor shall immediately notify the Contracting Officer. All drawings, specifications, operations and maintenance handbooks, manufacture's information, and other documents derived from the work, will belong to U.S. Army South and should be turned over as well as an original and two copies of the final construction and architectural drawings (as-builts). Format for the drawings shall be AutoCad 2010 and pdf. All designs required in this contract (new constructions and fabrication) shall be validated and approved by contractor professional license engineer and submitted to the COR for final approval. 5.2. Electrical Load Studies: The electrical load calculation for the CMSE house shall show electrical demand load in accordance with Article 220 of the 2011 National Electrical Code or equivalent Colombian Electrical Code. The load demand will helps to provide an accurate, consistent, and simplified method of determining the minimum size electrical service for the power generator. The demand loads shall take into account various probabilities of simultaneous operation of electrical appliances, equipments, computers, air conditioner units, and potential future demand of 20 percent. The recommended load studies shall include solutions that are safety/fire hazard free. 5.3. Back-up power generator: The back-up power generator system shall be designed and installed in accordance with NFPA 30, Flammable and Combustible Liquids Code, NFPA 37, Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines, NFPA, National Electric Code, and NFPA 110, Standard for Emergency and Standby Power Systems. Back-up power system shall consist of a diesel-engine (or a fuel sources common in the area of Tumaco) generator set with an automatic transfer switch. Generator set shall be completely enclosed in a weather resistant, corrosion resistant enclosure produced by the generator set manufacturer. The generator shall support the following loads: emergency lighting, computer, refrigeration and freezer, furnace, air conditioning, lighting - inside and outside, clean water for drinking and bathing, water pump, sump pump, kitchen appliances, cell phone chargers, Televisions, radios, washer, dryer, security system, garage door opener, fans, and other electric items. Minimum generator capacity shall be 40 KW. Voltage and frequency shall match that of the house power supply. The generator and power supply provided by the Contractor must have a factory representative and part supplies warehouse located in Colombia. The generator shall provide backup power for the entire house during emergencies only. 5.3.1 Reserve fuel tank. The generator shall contain a sub-base day tank and a reserve fuel tank. The reserve fuel tank shall be sized to store the volume of fuel required to run the generator at full load for 168 hours (seven 24-hour days). The main tank shall be above ground, single wall type with full concrete containment pad and curbing. Designer shall calculate specific equipment loads for the generator. The system shall be capable of powering the emergency lighting and power loads within 10 seconds of power failure. Automatic transfer switch shall be supplied to switch power from normal electrical distribution system and the emergency generator. Generator and service shall be sized for full load of the equipment and 20 percent spare capacity. The preferred generating voltage shall be the highest utilization voltage proposed for the facility. The set shall conform to NFPA 37 Standard for the Installation of Combustion Engines and Gas. The set shall include automatic start-and stop equipment, solid state battery charger, and tanks and radiator as required. Manual test switch shall be provided for automatic transfer switch. Automatic transfer switch shall be of double throw construction. Switch shall be equipped with by-pass isolation for maintenance purposes. The engine-generator shall be quiet operation. Engine-generator set shall be provided with a vibration-isolation system in accordance with the manufacturer's standard recommendation. Vibration isolation systems shall be designed and qualified (as an integral part of the base and mounting system) to the seismic zone specified in previous sections. Power generation package and all components shall be provided by a single manufacturer and installed complete and totally functional, with all necessary ancillary equipment. 5.3.2 The generator set shall include, at a minimum, the following components:
A. Packaged diesel-engine generator set (Contractor shall ensure to search the fuel sources available in Tumaco and provide a generator that can be easily fueled).
B. Generator main circuit breaker, instrumentation, controls, protection, and isolation
C. Automatic transfer switch
D. Factory provided corrosion resistant weather enclosure
E. Starting system
F. Air intake louvers, exhaust louvers, dampers, etc.
G. Cooling system
H. Fuel supply system with sub-base day tank
I. Above ground main fuel storage tank (to sustain 24hr/7 for a week). This storage tank shall be installed in a self-contained spillage prevention pool. Pool shall be designed to contain potential leakage to the tank capacity.
J. Exhaust system
K. Lubrication system
L. Concrete base structure for mounting the generator
M. Vibration isolation
N. Seismic protection
O. Main fuel tank concrete base and 100% fuel containment area
P. Shut-off valve with redundancy system
Q. Framed Instructions
R. Fire Extinguisher
S. Grounding and lighting protection system for the back-up power generator, fuel tank, and generator and fuel tank shacks.
The bid deadline for Generators With Installation was 11 May 2015. Bidding is closed.
This tender has been issued by Department of the Army in Colombia.
The tender value is not disclosed; please refer to the tender document. EMD / bid security details are provided in the tender document.
This tender is Self Financed
The tender is classified under the following CPV code(s): 31161300 - Generator rotors.
The tender notice and related documents are listed in the Documents section above. Select a document to view or download it. Please log in or register to access the documents. If you cannot find additional documents in the Documents section, please log in to your account and Send Document Request from your account section.
The TendersOnTime reference is 2872806. The purchaser document reference is W913FT15T0020.
Browse other tenders from Colombia or search by relevant keywords and CPV classification.
This tender falls under Defence and Security in Colombia. Suppliers in these sectors can track similar Colombia tenders using CPV-based alerts.