The PROVINCE OF ILOILO has issued a Tender notice for the procurement of a Bvh-17-2335-Np(Tf) Proposed Completion of Or/Dr Complex at Barotac Viejo District Hospital, Barotac Viejo, Iloilo in the Philippines. This Tender notice was published on 13 Aug 2018 and is scheduled to close on 17 Aug 2018, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 25797932, while the tender notice number is BVH-17-2335-NP(TF) and Registering on the platform.

Expired Tender

Procurement Summary

Country: Philippines

Summary: Bvh-17-2335-Np(Tf) Proposed Completion of Or/Dr Complex at Barotac Viejo District Hospital, Barotac Viejo, Iloilo

Deadline: 17 Aug 2018

Posting Date: 13 Aug 2018

Other Information

Notice Type: Tender

TOT Ref.No.: 25797932

Document Ref. No.: BVH-17-2335-NP(TF)

Competition: ICB

Financier: Self Financed

Purchaser Ownership: -

Tender Value: Refer Document

CPV Classification

71541000 - Construction project management services

Purchaser's Detail

Name: Login to see tender_details

Address: Login to see tender_details

Email: Login to see tender_details

Login to see details

Tender Details

Bvh-17-2335-Np(Tf) Proposed Completion of Or/Dr Complex at Barotac Viejo District Hospital, Barotac Viejo, Iloilo
Republic of the Philippines
Province of Iloilo
BIDS AND AWARDS COMMITTEE
INVITATION FOR NEGOTIATED PROCUREMENT
(TWO FAILED BIDDINGS)
Proposed Completion of OR/DR Complex at Barotac Viejo District Hospital, Barotac Viejo, Iloilo
RFQ. No. BVH-17-2335-NP(TF)
DATE: AUGUST 9, 2018
TO: ______________________________
______________________________
(Supplier's Name and Office Address)
In view of the two failed biddings held last April 18, 2018 and July 4, 2018, the Iloilo Provincial Government (IPG), through its Bids and Awards Committee (BAC), invites PhilGEPS-registered suppliers under Platinum category to participate in the negotiation for the project Proposed Completion of OR/DR Complex at Barotac Viejo District Hospital, Barotac Viejo, Iloilo in accordance with Section 53.1 of the revised Implementing Rules and Regulations of R.A. No. 9184, otherwise known as the Government Procurement Reform Act."
Following completion of the negotiations, kindly submit a best offer based on the final technical and financial requirements of the item(s) listed below, subject to the attached Terms and Conditions, stating the shortest time of delivery, and submit your bid duly signed by your authorized representative on or before the opening of quotations/bids on August 17, 2018 at 9:00 AM with the Bids and Awards Committee at the Boardroom, Office of the Governor, 3F, New Iloilo Provincial Capitol, Bonifacio Drive, Iloilo City.
The schedule of key procurement activities for this contract is shown below:
Activities Place Date Time
Negotiation Conference Boardroom, Office of the Governor, 3F, New Iloilo Provincial Capitol, Bonifacio Drive, Iloilo City August 15, 2018 9:00 AM
Deadline of Submission of Bid Proposal and Opening of Bids Boardroom, Office of the Governor, 3F, New Iloilo Provincial Capitol, Bonifacio Drive, Iloilo City August 17, 2018 9:00 AM and 9:01 AM, Respectively
ATTY. DENNIS T. VENTILACION
BAC Chairperson
X All Bids must be complete. Partial Bids are allowed.
Item No. Quantity Unit Description Estimated Unit Cost Brand Name Over the Counter Price per Item Final Unit Price per Item Delivered to Destination Total Cost
1 1 Job Contract furnishing of labor, materials, tools, equipment and other incidentals necessary for the Proposed Completion of OR/DR Complex at Barotac Viejo District Hospital, Barotac Viejo, Iloilo. Works include Removal/Installation of Roofing (including re-painting of existing tiles), Carpentry Works, painting Works, Room Signages, Electrical Works, Air conditioning System and installation of Fire protection System as per plan and specifications. 6, 263, 545.00
TERMS AND CONDITIONS
1. Contract period shall be One hundred Eighty (180) calendar days.
2. Winning bidder shall start the work five (5) days upon the receipt of Notice to Proceed (NTP).
3. Winning bidder shall inform the office of the Provincial Engineer in writing five (5) days prior to start of work.
4. Contractor shall provide safety precaution during work and shall be liable for the damages to person/property arising from the execution of work.
5. Liquidated damages shall be charged to the Contractor for every day of delay as provided in RA 9184.
6. Work shall conform to the approved plans and specifications.
7. All materials shall be delivered on the job site and inspected by the Project-In-Charge prior to start of work.
8. Contractor must observe cleanliness in the job site upon the acceptance, during and after completion of work.
Kindly indicate the DELIVERY PERIOD and BID AMOUNT IN WORDS and FIGURES in the space provided below. Non-compliance shall be a ground for DISQUALIFICATION.
TOTAL BID AMOUNT IN FIGURES: a‚+/-_______________
Statement of Delivery Period: __________________________________________________________________________
Bid Amount in Words: ________________________________________________________________________________
Place of Delivery: ___________________________
ABC: a‚+/- 6, 263, 545.00
Kindly submit your best offer with the following requirements:
1. PhilGEPS Certificate of Registration under Platinum category;
2. Omnibus Sworn statement specifying the RFQ Number for procurement projects with ABC above a‚+/-50, 000.00;
3. Notarized Authority of the Signatory, if representative (SPA of proprietor for single proprietorship/Secretary's Certificate for Corporation);
4. Updated Mayor's Permit if the same is indicated as "EXPIRED" in the PhilGEPS Certificate of Registration, Platinum category. For expired Mayor-s Permit, the official receipt as proof that the supplier has applied for renewal will be accepted, provided, that the renewed permit will be required as a post-qualification requirement;
5. Updated DTI/SEC/CDA Registration if the same is indicated as "EXPIRED" in the PhilGEPS Certificate of Registration, Platinum category;
6. For the procurement of Infrastructure Projects, bidders must submit a valid Philippine Contractors Accreditation Board (PCAB) License and indicate compliance with the Manpower Requirements;
7. Updated Tax Clearance if the same is indicated as "EXPIRED" in the PhilGEPS Certificate of Registration, Platinum category;
8. Income or Business Tax Returns for procurement projects with Approved Budget for the Contract (ABC) above a‚+/-500, 000.00.
9. Audited Financial statements, showing, among others, the prospective total and current assets and liabilities, stamped -œreceived- by the BIR or its duly accredited and authorized institutions, for the preceding calendar year which should not be earlier than two (2) years from the date of submission; for the type and cost of the contract to bid.
10. Statement of all its on-going contracts government and private contracts including contracts awarded but not yet started, if any. The statement shall include, for each contract, the following: (a) Name/Date of the Contract (b) Contract Duration (c) Owner-s Name & address (d) Nature of work (e) Contractor-s Role (f) total contract value (g) Percentages of planned and actual accomplishments and (h) value of outstanding works. The statement shall be supported by a Notice of Award or Notice to Proceed issued by the Owner.
11. Statement of the Single Largest Completed Contract (SLCC) government and private contracts. The statement shall be the following: (a) Name/Date of the Contract (b) Contract Duration (c) Owner-s Name & address (d) Nature of work (e) Contractor-s Role (f) total contract value at completion. The statement shall be supported by THE CERTIFICATES OF Completion and Acceptance issued by the Owner; or Constructors Performance Evaluation System (CPES) rating sheets & Notice to Proceed issued by the Owner.
12. NFCC Computation
13. Valid Joint Venture (JVA) or, lieu thereof, duly notarized statements from all the potential Joint Venture partners stating that they will enter into and abide by the provisions of the JVA in the instance that the bid is successful shall be included in the bid.
14.
Bid Security ( ) Sufficient ( ) Insufficient
15. Project Requirements, which shall include the following:
a. Organizational Chart for the Project
b. List of contractor-s personnel (ex. Project Manager, Project engineers, Materials Engineers and Foremen, to be assigned to the contract to be bid, with their complete qualification and experience data.
c. List of contractor-s equipment units, which are owned, leased, and/or under purchase agreements, supported by certification of availability of equipment lessor/ vendor or the duration of the project.
Note:
1. The Bids and Awards Committee may require additional documents/requirements agreed upon during the negotiation conference.
2. Kindly indicate the RFQ Number and date of opening of bids on the outside of the envelope.
Province of Iloilo
Bids and Awards Committee
Request for Price Quotation No: BVH-17-2335-NP (TF)
Reference PR No: BVH-17-2335
Terms and Conditions:
1. All entries must be filled-up, written, or printed legibly. Failure to use this form will result to disqualification of your bid.
2. Delivery period: within ONE HUNDRED EIGHTY (180) calendar days upon receipt of the Notice to Proceed.
3. Bids and bid securities shall be valid for one hundred twenty (120) calendar days from the date of the opening of bids.
4. Bids exceeding from the Approved Budget for the Contract (ABC) shall be disqualified.
5. The participating bidder/supplier or an authorized representative must indicate an active email address or working fax number. Absence of both shall be a ground for disqualification. Notice to the bidder through either of these means (email/working fax number) is considered sufficient notice.
6. The supplier must indicate its complete business/mailing address. Otherwise, the lack thereof is a ground for disqualification.
7. The supplier/awardee(s) must conform to the Notice of Award within three (3) calendar days from notice of such award and enter into contract with the Procuring Entity within ten (10) calendar days from receipt by the winning bidder of the Notice of Award. Otherwise, the award shall be forfeited or cancelled.
8. The AWARDEE shall be responsible for the source(s) of his supplies, materials, equipment and shall make deliveries in accordance with the schedule, quality and specifications of award and purchase order. Failure of the AWARDEE to comply with the same shall be ground for the cancellation of the award and purchase order issued to the AWARDEE.
9. All deliveries by suppliers shall be subject to inspection and acceptance by the representative of the General Services Office and End User.
10. Rejected deliveries shall be construed as non-delivery of the product(s)/item(s) so ordered and shall be subject to liquidated damages, subject to the terms and conditions prescribed under paragraph 11 hereof.
11. Supplier shall guarantee his deliveries to be free from defects. Any defective item(s)/product(s) therefore that may be discovered by the End-User within the warranty period after acceptance of the same shall be replaced by the supplier within seven (7) calendar days upon receipt of a written notice to that effect.
12. Performance Security or Warranty Security, as the case may be, shall be required from the winning bidder in accordance with the provisions of R.A. No. 9184 and its revised Implementing Rules and Regulations.
13. When an occurrence of a tie among bidders takes place, i.e., two or more of the bidders are determined and declared as the Lowest Calculated and Responsive Bidder (LCRB), the winning bidder shall be determined by draw lots upon notice to the bidders concerned and/or their authorized representatives in accordance with the relevant circulars issued by the Government Procurement Policy Board (GPPB).
14. All offers/quotations must be properly sealed and marked in envelopes. Non-compliance is a ground for disqualification.
15. The printed name and signature of the bidder/supplier or of its authorized representative must be legible and verifiable and must indicate his/her position. Non-compliance is a ground for disqualification.
16. Bidders shall prepare an ORIGINAL of the Documentary Requirements for Negotiated Procurement. In addition, bidders shall submit separate COPIES thereof (Copy 1, Copy 2) and each set of documents must clearly indicate whether the same is ORIGINAL, COPY 1, or COPY 2. Non-compliance shall be a ground for declaration of FAILURE/DISQUALIFICATION. In the event of any discrepancy between the original and the copies, the original shall prevail.
MINIMUM KEY PERSONNEL REQUIREMENTS FOR
THE PROJECT
1- Project Engineer
1- Materials Engineer
1- Construction Foreman
1- Electrical Engineer
1- Safety & Health Officer
MINIMUM EQUIPMENT EQUIREMENT FOR THE PROJECT
1-UNIT- CONCRETE MIXER
1-UNIT-CONCRETE VIBRATOR
1-UNIT- ELECTRIC DRILL
1-UNIT-ELECTRIC SANDER
1-UNIT-WELDING MACHINE
Specifications
GENERAL REQUIREMENTS
All works to be done shall be with first class workmanship and shall conform to plans and Specifications. All materials to be use shall be of good quality and properly inspected by the authorized representative or the Engineer In-Charge. The Provincial Engineer is reserved the right to rescind, terminate, suspend the contract if he deems necessary and to the best interest of the Government. The contractor shall be liable for all damages that will occur during the construction of the project.
SCOPE OF WORKS
Works include Removal/Installation of Roofing (including re-painting of existing Trusses), Ceiling Works (including removal of existing Ceiling), Tile Works (including removal of existing Tiles), Carpentry Works, Painting Works, Room Signages, Electrical Works, Airconditioning System and Installation of Fire Protection System as per plan and specifications.
I. Removal/Installation of Roofing
II. Ceiling Works (Including Removal of Existing Ceiling)
- Ceiling Board
- Metal frame/joist
III. Tile Works (Including Removal of Existing Tiles)
IV. Carpentry Works
- Closet, Counter, Hanging Cabinet & Nurses Station
- Drywall Partition
- Tables & Chairs
- Swing Steel Louver Door
V. Painting Works
Interior walls
Exterior Walls
Ceiling
Closet, Counter, hanging Cabinet & Nurses Station
VI. Room Sinages
VII. Electrical Works
VIII. Mechanical Works
- Air-conditioning System
- Installation of Fire Protection System
Outline Specifications
I. REMOVAL/INSTALLATION OF ROOFING
All materials shall be of the kind size specified on the plans. All works shall be performed and computed in accordance with the generally accepted and modern practice of roofing. Use materials as specified in the plan. All welding shall be done by approved, competent, experienced and fully qualified welders. Surfaces to be welded shall be smooth, uniform and free from fins, tears and other defects, which would adversely affect the quality of the weld. The contractor shall remove and replace or correct as instructed and welds found to be defective or deficient. He shall also replace all methods found to produce inferior results with methods that will produce satisfactory work. For the installation of downspout use 3- dia. PVC Pipe series 1000 with G.I. strap spaced at 1.0m on center & for the Insulation use double sided with 10mm thick. Use pre-painted long span for roofing. After removal of existing roofing all existing trusses shall be re-painted by red oxide before install new ones. See plans and details.
II. CEILING WORKS
The works include removal of existing ceiling as per indicated in the plan. All existing structures/utilities not to be replaced or repaired shall be protected from any damage by any work being done. Materials to be used for ceiling board shall be 3.5mm thick Hardilite attached to 19mm x 50mm, 0.40mm metal furring channel & 25mmx25mm, 0.40mm Wall angle. Metal furring shall be attached with W-clip to 12mmx38mm, 0.80mm Carrying channel spaced @ 1.20m. All spaced @ 0.40m on wall side the rest @ 0.60m center both ways. Hanger shall be #12 tie wire spaced @ 1.20m on center both ways. Electrical System such as lightning fixtures and wiring shall be restored upon completion of the ceiling works. See plan for dimension and details.
III. TILE WORKS
The works include chipping of tiles as per indicated in the plan. All existing structures/utilities not to be replaced or repaired shall be protected from any damage by any work being done. Tiles shall be soaked in clean water prior to installation for a minimum of one hour. Mortar mix for scratch coat and setting bed shall consist of one part cement and 3 parts sand by volume or use Tile adhesive (Heavy Duty) for mortar. Determine and mark layout of tiles as to joint location, position of trims and fixtures so as to minimize cutting less than one half size of the tile. Thoroughly dampen surface to be tiled but not to saturate the surface. Apply and spread mortar mix for setting bed and tamp to assure good bond over the entire area to be laid with tile. Allow setting bed to set sufficiently, then spread a bond coat over the surface and lay the tile. Grouting mortar shall be applied over the tile by float or squeegee stroked diagonally across the joints. Remove excess mortar with wet sponge stroked diagonally or circular motion after 12-15 minutes. Follow with a barely damp or dry sponge to remove remaining haze while smoothing all grouted joints. Use granite tiles for the installation of 0.10m x 0.60m baseboard molding. Use In-Laid Vinyl Sheet for wall code: 2063 Emerald at 1.0m height from finish floor line with in-laid vinyl sheet mural plus 3011 up to ceiling line with in-laid vinyl for flooring, Code: 2054 Cloud. The color of the tiles shall be referred to the end-user or the Engineer in charge. See plans for dimension and details.
IV. CARPENTRY WORKS
1. Execute rough carpentry in best, substantial, workmen like manner, erect framing true to
Line, levels and dimensions, squared, aligned, plumbed, well spliced, nailed and adequately braced, properly fitted using mortise and lenon joists.
Finish carpentry shall be absolutely kiln dried lumber and water proofed marine plywood. Finishes lumber shall be S2S or S4S.
Joinery details- various types of joints are used for millwork construction to increase the strength of the joint and improve the appearance by eliminating mechanical fasteners such as screws. With the availability of high strength adhesives, screws and other mechanical fasteners are seldom needed for the majority of the work produced in the shop. Field attachment, however, often requires the use of blind nailing or other concealed fastening to maintain the quality look of the work.
Materials to be used for cabinets shall be, A3/4-thick Marine Plywood framed w/ 2-x2- (S4S) & 2-X3- (S4S). For Nurse Desk use A3/4- granite slab for counter top & A3/4- granite splash board with A3/4- Marine Plywood protruding. Provide necessary fittings such as cabinet hinges, catches, drawer guide, and handle (good quality). Apply wood glue to ensure fixedness. See plan for dimensions and details.
For additional drywall partition use 6.0mm thick x 4-x 8- Cement Board on 0.5mm x 35mm x 76mm Metal Tracks and 0.5mm x 32mm x 76mm Metal Studs space at 0.40m on center.
Use fabricated steel louver door with 4-sets stainless heavy duty hinges and steel door jamb to be installed at EE Room.
V. PAINTING WORKS
Paints to be used shall be Boysen, Davies or any equivalent in brand
All painting materials shall meet the requirements of standard specifications and subject for the approval by the supervising engineer. All paints shall be delivered at the jobsite in the original containers with label intact and seals unbroken. Surface to be painted shall be clean smooth and rid of dust, dirt, rust, chalk, grease, wax polishes, alkali and other foreign matter. Old paint shall be remove stripped using scraping, wire brushing and sanding, repair all voids, nicks, cracks with suitable patching materials.
Masonry surfaces (Interior & Exterior)
1st Coat - Flat Latex
2nd & 3rd Coat - Semi Gloss Latex
Ceiling
1st Coat - Flat Latex
2nd & 3rd Coat - Semi-gloss Latex
Closet, Counter, hanging Cabinet & Nurses Station
1st Coat - Lacquer Primer Surface
2nd & 3rd Coat - Gloss Lacquer Enamel
All works shall be done in workmanlike manner by skilled painter. No painting shall be thoroughly stirred so as to keep the pigments spread evenly when paint is being applied to the surface. All coats shall be thoroughly dry first before application of succeeding coat.
The Contractor shall include in his work all clean-up of paint on the floor.
VI. ROOM SIGNAGES
All materials shall be of the kind size specified on the plans. Vinyl Sticker background color green on 3mm thick acrylic sheet with vinyl sticker letters cut-out color white avant garde-book bold font. Use #10 decorative hanging chain chrome pin with # 1- coated cup hook (white) attach at ceiling for the installation of directional signage.
VII. ELECTRICAL WORKS
SCOPE OF WORK
The works include furnishing of labor, materials, tools, equipments and other incidentals necessary to complete the project such as: electrical works.
a. The work under this section consist of furnishing of labor, materials, equipment, Tools and all incidentals to complete and ready for use as indicated in the electrical plans for the project, in accordance with the drawing, specifications and contract.
1. Furnishing and installing all necessary sub-feeder and branch circuit wires necessary with corresponding sizes as indicated in electrical plans.
2. Furnishing and installing all necessary electrical wiring devices such as utilization outlets, wall switches, and receptacle all complete with their proper cover plates.
3. Furnishing and installing all necessary pull boxes, junction boxes, utility boxes and other type of box as site condition requires and /or as indicated in the plan.
b. All work hereunder, shall comply with the latest edition of the Philippine Electrical Code Part I, the rules and regulation of the Local Electric Ordinance of the locality, the rules and regulation of local government authorities and with the Republic Act 7920 as applied or enforced in the projects locality.
c. All installation work shall be done under the direct supervision of a duly licensed Registered Electrical Engineer as provided or employed by the contractor. Electricians undertaking the actual installation shall be as trained and certified by TESDA.
2.0 PRODUCTS
2.1 CONDUITS, FITTINGS AND BOXES
All wirings running through concrete ceiling or concrete partitions shall be in uPVC thickwall conduit, concealed and properly embedded. Conduit shall not be less than 20mm nominal diameter or as indicated in the plan. All conduits fittings shall be of the same brand with the conduit. Proper connection between conduits shall be observed by using PVC solvent cement Utility and junction boxes shall be PVC, heavy duty and deep type with brand the same with that of the conduits. Pull boxes and wire gutters as site condition would require its installation shall be gauge #18 and painted with gray epoxy primer finished in enamel gray paint. Sizes shall be subject for approval by the Electrical Engineer. All junction boxes, square boxes and pull boxes shall be provided with corresponding and appropriate cover.
2.2 WIRES AND CABLES
Branch circuit and main feeder lines shall be laid out in accordance with the diagrams as shown in the drawing. Unless otherwise specified in the specifications or shown in the drawings, type THHN wires shall be used to all branch circuit conductors. The wires as shown in the electrical plan shall be the minimum sizes to be used. Wires shall be as recommended by the Electrical Engineer. For service conductor tap shall be heavy duty, all brass and copper split bolt type solderless connectors and are tightened to the maximum mechanical strength and insulate with rubber friction tapes to ensure an insulation of the conductors they join. Branch circuit splicing and tapping for lighting and power junction and utility boxes shall be done using rubber tape and must be overlay by electrical plastic tape to limit moisture penetration. No splicing shall be permitted inside the conduits. Unless otherwise site condition requires such splicing, proper boxes shall be provided.
2.3 LIGHTING FIXTURE
All Lighting fixtures to be use shall be limited to Compact Fluorescent Lamp type. Outdoor globe luminaire with 18W 3U Compact Fluorescent Lamp shall have holder with full acrylic cover, outside aluminum guard with top cover, properly mount in the surface of the column top. Canopy lights shall be Compact Fluorescent lamp in painted cylindrical steel cover.
3.0 TEST AND ADJUSTMENTS
After the installation have been completed and when the system is ready for operation, insulation resistance testing and continuity test shall be conducted by a competent and experienced engineer to be furnished by the contactor. These tests shall demonstrate the insulation level of the wirings detecting any presence of grounded installations and short circuits. The contractor shall also furnish all the instruments such as multi-tester and insulation resistance tester to enable him to carry out a comprehensive test of the equipment and system.
VIII. AIRCONDITIONING SYSTEM
GENERAL
1. All mechanical work shall conform according to PSME Code of the Philippines.
2. All window type air-conditioning should be installed with 0.5 inclined back.
3. All Split type Air conditioning piping layout must be insulated with charole, rubber insulation and ACU brackets/pedestal.
4. All aircon drain line must be properly installed.
5. R-410A or R22 refrigerant should be used in all Airconditioning units
6. Provision of brackets for the indoor and 900mm ground level for the outdoor unit.
7. Outdoor Breakers should be provided for each Airconditioning units.
8. All aircon installer should be authorized installer of manufacturer.
9. All mechanical installation should be supervised by RME / PME according to
RA 8495 known as ME Law.
1.1 SCOPE
The contractor for the installation of the air conditioning system shall be a qualified contractor and installer, regularly engaged in the installation and must have at least one year experience on the trade. The work shall include the furnishing of all labor, materials, equipment and services necessary the complete installation, testing and commissioning of the system as per plan. In case of conflict between plans and this specification, the Architect/Consultant shall be notified. All permits and fees, private or government shall be secured by owner prior to the start of work. Furnish and install split and window type air-conditioning units as per plan and specification. System shall include piping installation, brackets and supports, circuit breaker wires, refrigerant piping and other to complete installation. Do all necessary civil works in the installation of outdoor and indoor unit window type Refrigerant piping shall be hard/soft drawn Type L, Refrigerant piping shall be insulated with 20 mm thickness cellular foam, flexible, cellular elastromeric molded in the suction lines and covered with canvass clothes or leather as vapor burners.
Drain pipe shall be UPVC of 15 mm schedule 50 and shall be insulated at least 2 meters from the unit with 10 mm rubber cellular elastromeric insulator. All piping shall be bracketed, supported, and hang at least every 3m on BI pipe and every 2m on copper piping. Refrigerant piping shall be pressured tested at least 1.5 times the operation pressure or at least 1.72 mpa and maintained for at least 1.72. Mpa and maintained for at least 8 hours. Refrigerant pipings after pressure testing shall be evacuated using triple evacuation prior to the charging.
SUBMITTALS
Product data/Manuals & Brochure: Within 35 calendar days after the Contractor has received the Owner-s Notice to Proceed, submit : Manufacturer-s specifications and other data needed to prove compliance with the Materials list of items proposed to be provided under this Section Specified requirements. Shop Drawings and other data as required indicating method of installing and attaching, except where such details are fully shown on the Drawings.
QUALITY ASSURANCE
Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work of this Section.
TEST & COMMISSIONING
Submit leak test results (with picture) prior to startup, start-up report should be submitted during and after the test and commissioning period for acceptance.
IX. INSTALLATION OF FIRE PROTECTION SYSTEM
SCOPE OF WORK
The works include furnishing of labor, materials, tools, equipments and other incidentals necessary to complete the project such as: Sprinkler System, Fire Department Inlet/Manifold Connection, Supply of Fire Hose Cabinet with glass & complete accessories (FHC), Miscellaneous & Consumables, Pumps & Accessories, Cistern tank & electrical works, Removal & Installation of Ceiling and Concrete Chipping/Finishing & Painting, electrical works (Fire Alarm Control System), and Testing & Commissioning & Training of Personnel per plan & specifications.
Contractor shall provide safety precaution during work and shall be liable for the damages to person/property arising from the persecution of work.
All materials shall be delivered on the jobsite and inspected by the Project in charge & MQC prior to the installation.
Contractor shall coordinate with Hospital Maintenance personnel and conduct Tool Box Meeting prior to execution of work.
GENERAL
1. All mechanical work shall conform according to PSME Code of the Philippines.
2. All pipe shall conform to ASTM standard APO brand or equivalent.
3. All installer for working should be certified welder by TESDA.
4. Fire Pump / Jockey Pump and all ACC for sprinkler system should be UL / FM Standard.
5. Pressure test at 200 PSI at 24 hours testing to maintain at 120 PSI working pressure.
6. All mechanical installation should be supervised by RME / PME according to
RA 8495 known as Mechanical Engineering Law.
7. Test and Commissioning should be done after the whole system is fully operation (online).
1.1 SCOPE
a. The contractor for the installation of the fire protection system shall be a qualified contractor and installer, regularly engaged in the installation and must have at least one year experience on the trade. The work shall include the furnishing of all labor, materials, equipment and services necessary the complete installation, testing and commissioning of the system as per plan. In case of conflict between plans and this specification, the Architect/Consultant shall be notified. All permits and fees, private or government shall be secured by owner prior to the start of work. Furnish and install fire protection system as per plan. System shall include piping installation, brackets and supports, circuit breaker wires, refrigerant piping and other to complete installation. Do all necessary civil works in the installation of pipings for sprinkler system. Fire protection piping shall be BI pipe schedule 40 and welded connection for 50 mm and above. For 50 mm below maybe BI and threaded connection.
All piping shall be bracketed, supported, and hung at least every 3m on BI pipe Fire protection piping shall be hydrostatically tested to at least 0.6 Mpa Fire protection piping shall be painted with two coats of epoxy primer and finished with two coats of red enamel paints or as per required by code.
Hangers and supports and brackets shall be pre-painted with two coats of epoxy primer finished with two coats of aluminum or silver paint. BI pipe installed shall be painted with two coats and epoxy primer and finished with two coat of red enamel paint.
SUBMITTALS
Product data: Within 15 calendar days after the Contractor has received the Owner-s Notice to Proceed, submit :Manufacturer-s specifications and other data needed to prove compliance with the Materials list of items proposed to be provided under this Section Specified requirements. Shop Drawings and other data as required indicating method of installing and attaching, except where such details are fully shown on the Drawings.
QUALITY ASSURANCE
Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work of this Section.
General
The Contractor shall perform the work described, in the welding installation of all B.I. pipes should be done by a certified TESDA Class I. Pendant or downright type sprinkler be used in the area of open space and sidewall in case maybe. Sway Bracing for sprinkler will be installed in no column available in the area and Pipe bracket will also be installed in the area as to plans and specification. Pipe hanger properly installed to handle the wet type system according to table of dimension diameter. Sprinkler distance at least 290mm equidistance. Siamese twin hose header should be 900mm from the floor elevation with cap and chain strap. Alarm check valve assembly (for wet type) should be installed and supervisory for ground and second floor control valve assembly. Fire Hose Cabinet (FHC) is of surface mounted with 900mm from floor elevation with 750mm with, with 30m double jacketed 1 A1/2-A˜, with 4.5kg portable fire extinguisher and a fog type nozzle and Fire Ax.
All pipes will be of ERW ASTM standard schedule 40, sprinkler head will be UL/FM standard, hydrotesting should be at 7 bars at 24hrs. Testing and Commissioning shall be witnessed by the representative from Fire Department and the Professional Mechanical Engineer (PME) supervising the installation and test at least two sprinkler to be simulated for actual activation. Automatic sprinklers if required shall be in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems. All automatic sprinkler and standpipe systems required by this code shall be inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
Records of conducted maintenance and testing should be maintained. Sprinkler impairment procedures shall comply with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
A. Supervisory Signals
Where supervised automatic sprinkler systems are required by another Section of this Code, supervisory attachments shall be installed and monitored for integrity in accordance with NFPA 72, a distinctive supervisory signal shall be provided to indicate a condition that would impair the satisfactory operation of the sprinkler system. Monitoring shall include, but shall not be limited to, monitoring of control valves, fire pump power supplies and running conditions, water tank levels and temperatures, tank pressure, and air pressure on dry-pipe valves. Supervisory signals shall sound and shall be displayed either at a location within the protected building that is constantly attended by qualified personnel or at an approved, remotely located receiving facility.
B. Alarm Signal Transmission
Where supervision of automatic sprinkler systems is required, waterflow alarms shall be transmitted to an approved, proprietary alarm receiving facility, a remote station, a central station, or the fire station.
D. Valves.
Connections other than for fire service use shall be provided with an approved indicating-type valve and check valve located close to the supply such as tanks, pumps, and connections from waterworks system. Valves shall be provided to allow isolation of a standpipe without interrupting the supply to other standpipes from the same source of supply.
E. Pipe brackets and hangers.
Installation should be based on tables provided in the plans and specification in thickness, dimension and spacing for pipe support. Contractor shall provide safety precaution during work and shall be liable for the damages to person/property arising from the persecution of work
Supply of Fire Hose Cabinet with Glass & Complete Accessories (FHC)
Installation of Fire Hose Cabinet, surface mounted with brass nozzle fog adjustable, 1 A1/2- dia. X 30 meters long double jacketed with chrome pin lug coupling threaded, pull push mounting door with trim for all glass shall be guage # 18 wi note -œBRAKE GLASS IN CASE OF FIRE-, with 10 lbs or 4.5 kg. dry chemical type ABC portable Fire extinguishers with dimension of 750mm x 800mm, pipe connection should be 40mm diameter.
All one hundred millimeters (100 mm) dry standpipes shall be equipped with a four-way fire service connection. All fire service connections shall be located on a street front, not less than forty six centimeters (46 mm) or more than one hundred twenty two millimeters (122 mm) above grade and shall be equipped with an approved straight way check valve and substantial plugs or caps. All fire service connections shall be protected against mechanical injury and shall be visible and accessible. More than one fire service connection may be required.
A. - Inspector Test Connection should be installed with sprinkler heads for testing purposes by the Fire Department.
B. - Valves. Connections other than for fire service use shall be provided with an approved indicating-type valve and check valve located close to the supply such as tanks, pumps, and connections from waterworks system. Valves shall be provided to allow isolation of a standpipe without interrupting the supply to other standpipes from the same source of supply.
C. - Signs. Signs shall be provided. If automatic sprinklers are also supplied by the fire service connection, the sign or combination of signs shall indicate both designated services.
Schedule of Drawings
(Issued Separately)
Bill of Quantities
Bid No. BVH-17-2335-NP (TF)
Item Description Quantity Unit Unit Cost Total Cost
No.
I. Removal of Dilapidated 374.93 sq. m. Pesos
Of Roofing & Installation
Of 0.40mm Pre-Painted
Long Span Roofing and ctvs.
(Including Repainting (P ) / sq.m. P
Of Existing Trusses)
With 10mm thk.
Double Sided Insulation
Total for Item I P
II. Ceiling Works
A. Removal of 374.83 sq. m. Pesos
Existing Ceiling
and ctvs.
(P ) / sq. m. P
A) Interior Ceiling 298.19 sq.m. Pesos
Fibercement Board on
Metal furring and ctvs.
(P ) / sq.m. P
B) Exterior Ceiling 75.65 sq.m. Pesos
Fibercement Board on
Metal furring and ctvs.
With Air Vent & Wire (P ) / sq.m. P
Mesh
Total for Item II P
III. Tile Works
1. Removal of Existing 290.77 sq m. Pesos
Tiles
and ctvs.
(P ) / sq m. P
2. 0.60mx0.60m Polish 117.23 sq m. Pesos
Granite Tiles
and ctvs.
(P ) / sq m. P
3. In-Laid Vinyl Tiles 173.55 sq m. Pesos
(Floor)
and ctvs.
(P ) / sq m. P
Total for Item III P
Item Description Quantity Unit Unit Cost Total Cost
No.
4. In-Laid Vinyl Sheet 119.39 sq m. Pesos
(Wall) including Cove
Former Capping Strip and ctvs.
(P ) / sq m. P
5. In-Laid Vinyl Sheet 92.80 sq m. Pesos
(Mural)
and ctvs.
(P ) / sq m. P
6. 0.30mx0.30m Rustic 2.27 sq m. Pesos
Floor Tiles
and ctvs.
(P ) / sq m. P
7. Baseboard Moulding 22.82 sq m. Pesos
Granite Tiles
and ctvs.
(P ) / sq m. P
Total for Item III P
IV. Carpentry Works
A. Closet, Counter, Hanging Cabinet & Nurse Station
A.1 Closet
1. 0.50m x 1.80m x 2.10m 3.00 Sets Pesos
Closet Cabinet w/ A3/4-
Thk marine plywood and ctvs.
w/ cabinet lock, (P ) / sq m. P
Cabinet handle & hanger stainless rod
A.2 Filing Cabinet
1. 0.50m x 2.00m x 1.80m 2.00 sets Pesos
Filling Cabinet w/ A3/4-
Thk marine plywood and ctvs.
w/ 6mm thk clear glass (P ) / set P
Sliding door on standard aluminum frame w/ cabinet lock
A.3 Hanging Cabinet
Item Description Quantity Unit Unit Cost Total Cost
No.
1. 0.30m x 2.00m x 0.80m 1.00 set Pesos
Hanging Cabinet w/ A3/4-
Marine Plywood w/ and ctvs.
6mm thk clear glass (P ) / set P
Snap on (magnetic) door on standard aluminum frame
2. 0.3m x 1.80m x 0.80m 1.00 set Pesos
Hanging Cabinet w/ A3/4-
Marine Plywood w/ and ctvs.
6mm thk clear glass (P ) / set P
Snap on (magnetic) door on standard aluminum frame
3. 0.30m x 1.90m x 0.80m 1.00 set Pesos
Hanging Cabinet w/ A3/4-
Marine Plywood w/ and ctvs.
6mm thk clear glass (P ) / set P
Snap on (magnetic) door on standard aluminum frame
4. 0.30m x 2.90m x 0.80m 1.00 set Pesos
Hanging Cabinet w/ A3/4-
Marine Plywood w/ and ctvs.
6mm thk clear glass (P ) / set P
Snap on (magnetic) door on standard aluminum frame
5. 0.30m x 1.90m x 0.80m 1.00 set Pesos
Hanging Cabinet w/ A3/4-
Marine Plywood and ctvs.
(P ) / set P
6. 0.30m x 0.60m x 4.90m 1.00 set Pesos
Hanging Cabinet w/ A3/4-
Marine Plywood w/ and ctvs.
6mm thk clear glass (P ) / set P
Snap on (magnetic) door on standard aluminum frame w/ 0.55m x 0.70m x 4.90m counter cabinet w/ lock & handle
Item Description Quantity Unit Unit Cost Total Cost
No.
A.4. Repair of Cabinets
1. 0.30m x 0.60m x 2.65m 1.00 set Pesos
Replace existing marine
Plywood hanging and ctvs.
Cabinet w/ 6mm thk (P ) / set P
Clear glass snap-on (magnetic) door & repair of counter cabinet w/ piano hinges & cabinet handle
2. 0.60m x 0.65m x 2.65m 1.00 set Pesos
Replacement of existing
Marine plywood and ctvs.
Counter cabinet w/ (P ) / set P
Hinges & cabinet handle and installation of A3/4- thk granite slab counter top/skirting & splash board
A.5
Counter
1. Nurses Station Counter 1.00 set Pesos
w/ 3/4- granite slab
Counter top A3/4- thk and ctvs.
Granite slab splash (P ) / set P
Board & A3/4- marine plywood protruding
Total for A P
B. Dry Wall Partition 8.82 sq m. Pesos
and ctvs.
(P ) / sq m. P
Total for B P
C. Swing Steel Louver 1.00 set Pesos
Door
(0.80m x 2.10m and ctvs.
Fabricated Steel Louver (P ) / set P
Door w/ 4 sets stainless heavy duty hinges & steel door jamb)
Total for C P
Total for Item IV P
Item Description Quantity Unit Unit Cost Total Cost
No.
V. Painting Works
a) Wall Surface 994.25 sq.m. Pesos
and ctvs.
(P ) / sq m P
b) Ceiling Surface 492.53 sq.m. Pesos
and ctvs.
(P ) / sq m P
c) Closet, Counter, 173.65 sq.m. Pesos
Hanging Cabinet &
Nurses Station and ctvs.
(P ) / sq m P
Total for Item V P
VI. Room Signages (Including Labor & Installation)
a) Vinyl sticker 3, 406.61 sq. in. Pesos
Background 0n 3mm
Thk acrylic sheet and ctvs.
(Signages) (P ) / sq. in. P
b) 0.40m x 1.0m vinyl 2.00 Sets Pesos
Sticker background on
3mm thk acrylic sheet and ctvs.
(Signages) w/ # 10 (P ) /set P
Decorative hanging chain chrome pin w/ complete accessories
Total for Item VI P
VII. Electrical Works
A. Chipping & Tapping of Concrete Wall
a) Chipping of Concrete 0.34 Cu.m. Pesos
Wall
and ctvs.
(P ) / cu.m. P
Item Description Quantity Unit Unit Cost Total Cost
No.
b) Concrete Topping 0.34 Cu.m. Pesos
and ctvs.
(P ) / cu.m. P
Total for Item A P
a. Panel Board
1 Main: 200AT/250AF, 1.00 Unit Pesos
3P, 230Vac ECB
and ctvs.
(P ) / unit P
2 Main: 125AT/225AF, 1.00 Unit Pesos
3P, 230Vac MCCB
and ctvs.
(P ) / unit P
3 Branches: 14.00 Pcs Pesos
20AT/50AF, 2P 250Vac,
Circuit Breaker and ctvs.
(10KAIC) MCB Bolt-on (P ) / pc P
type
4 18-Holes NEMA1 1.00 Unit Pesos
Enclosure wall surface
Mounted 3A˜ Main and ctvs.
20KA bus bracing with (P ) / unit P
Gounding terminal
5 Main: 100AT/100AF, 1.00 Unit Pesos
3P, 230Vac MCCB
and ctvs.
(P ) / unit P
6 Branches: 16.00 Pcs Pesos
20AT/50AF 2P, 250Vac,
(10KAIC), MCB, and ctvs.
Bolt-on type (P ) / pc P
7 18-Holes NEMA1 1.00 Unit Pesos
Enclosure wall surface
Mounted 3A˜ Main and ctvs.
20KA bus bracing with (P ) / unit P
Gounding terminal
Item Description Quantity Unit Unit Cost Total Cost
No.
b. Lighting Fixture
1 2 x 28W T5 flourescent 39.00 Pcs Pesos
Lamp with aluminum
reflector and ctvs.
(P ) / pc P
2 2 x 20W T8 recessed 25.00 Pcs Pesos
Type dustproof
luminaire and ctvs.
(P ) / pc P
3 18W LED Downlight 3.00 Pcs Pesos
and ctvs.
(P ) / pc P
4 12W LED Downlight 1.00 Pc Pesos
and ctvs.
(P ) / pc P
5 7W LED Downlight 2.00 Pcs Pesos
With glass cover
and ctvs.
(P ) / pc P
6 Chandelier 1.00 Unit Pesos
and ctvs.
(P ) / unit P
7 150W exhaust fan 27.00 Units Pesos
and ctvs.
(P ) / unit P
8 2 x 3W dual optic 17.00 Units Pesos
Emergency Light
and ctvs.
(P ) / pc P
Item Description Quantity Unit Unit Cost Total Cost
No.
9 Orbit Fan 2.00 units Pesos
and ctvs.
(P ) / unit P
10 Fire Exit Light 6.00 units Pesos
and ctvs.
(P ) / unit P
c. Wiring Device
1 One gang switch, wide 11.00 sets Pesos
Series
and ctvs.
(P ) / set P
2 Two gang switch, wide 18.00 sets Pesos
series
and ctvs.
(P ) / set P
3 Three gang switch, wide 3.00 sets Pesos
series
and ctvs.
(P ) / set P
4 Three way switch, wide 8.00 sets Pesos
series
and ctvs.
(P ) / set P
5 Dimmer Type switch 1.00 set Pesos
and ctvs.
(P ) / set P
d. Power Device
1 Single receptacle outlet, 14.00 sets Pesos
Wide series
and ctvs.
(P ) / set P
Item Description Quantity Unit Unit Cost Total Cost
No.
2 Duplex receptacle outlet 23.00 sets Pesos
(grounding type)
and ctvs.
(P ) / set P
3 Special purpose outlet, 20.00 sets Pesos
(grounding type)
and ctvs.
(P ) / set P
4 Automatic sensor type 6.00 sets Pesos
Hand Dryer
and ctvs.
(P ) / set P
e. Wires & Cables
1 2.0 sq.mm.THHN/ 3.00 rolls Pesos
THWN copper wire
and ctvs.
(P ) / roll P
2 3.5 sq.mm.THHN/ 19.00 rolls Pesos
THWN copper wire
and ctvs.
(P ) / roll P
3 8.0 sq.mm. THHN/ 130.00 meters Pesos
THWN copper wire
and ctvs.
(P ) / meter P
4 22.0 sq.mm. THHN/ 60.00 meters Pesos
THWN Copper wire
and ctvs.
(P ) / meter P
5 30.0 sq.mm. THHN/ 60.00 meters Pesos
THWN Copper wire
and ctvs.
(P ) / meter P
Item Description Quantity Unit Unit Cost Total Cost
No.
6 80.0 sq.mm. THHN/ 480.00 meters Pesos
THWN Copper wire
and ctvs.
(P ) / meter P
F. Conduit & Fittings
1 20mmA˜ uPVC flexible 2.00 roll Pesos
conduit
and ctvs.
(P ) / roll P
2 20mmA˜ Electrical PVC 210.00 length Pesos
Pipe
and ctvs.
(P ) / length P
3 32mmA˜ Electrical PVC 3.00 length Pesos
Pipe
and ctvs.
(P ) / length P
4 75mmA˜ PVC 45A elbow 98.00 pcs Pesos
and ctvs.
(P ) / pc P
5 75mmA˜ PVC 45A wye 33.00 pcs Pesos
reducer
and ctvs.
(P ) / pc P
6 75mmA˜ PVC flexible 50.00 meters Pesos
conduit
and ctvs.
(P ) / meter P
7 75mmA˜ PVC conduit 15.00 length Pesos
and ctvs.
(P ) / lenght P
Item Description Quantity Unit Unit Cost Total Cost
No.
8 100mmA˜ PVC conduit 40.00 length Pesos
and ctvs.
(P ) / lenght P
G. Boxes & Pull Boxes with cover
1 PVC Utility Box 136.00 pcs. Pesos
(2- x 4- )
and ctvs.
(P ) / pc P
2 PVC Octagonal Box 244.00 pcs. Pesos
(4- x 4- )
and ctvs.
(P ) / pc P
3 PVC Pull Box 10.00 pcs. Pesos
(4- x 4- )
and ctvs.
(P ) / pc P
h. Miscellaneous 1.00 lot Pesos
(PVC Electrical Tapes,
PVC elbows, PVC tees, and ctvs.
Tie wires, Solvent (P ) / lot P
Cement, solderless connectors, expansion bolts, adaptors, & locknuts)
X. Fire Alarm/Auxiliary System (Ground & Second Floor
1 Conventional smoke 27.00 pcs Pesos
Detector
and ctvs.
(P ) / pc P
2 F/A Bell 6- wall surface 2.00 units Pesos
Mounted
and ctvs.
(P ) / unit P
Item Description Quantity Unit Unit Cost Total Cost
No.
3 Fire Alarm Switch 3.00 units Pesos
and ctvs.
(P ) / unit P
4 6-Zone Fire Alarm 1.00 unit Pesos
Panel
and ctvs.
(P ) / unit P
5 1.6 sq. mm CAT5 E 2.00 rolls Pesos
Wire
and ctvs.
(P ) / roll P
6 22 AWG twisted pair 150.00 meters Pesos
Telephone wire
and ctvs.
(P ) / meter P
7 Telephone outlet 1.00 set Pesos
and ctvs.
(P ) / set P
8 Inter/LAN Outlet 13.00 sets Pesos
and ctvs.
(P ) / set P
9 20mmA˜ Electrical PVC 25.00 length Pesos
Pipe
and ctvs.
(P ) / length P
9 20mmA˜ uPVC flexible 1.00 roll Pesos
Conduit
and ctvs.
(P ) / roll P
Item Description Quantity Unit Unit Cost Total Cost
No.
10 Miscellaneous 1.00 lot Pesos
(PVC fittings, adaptor,
G.I. wires, cable ties and ctvs.
etc) (P ) / lot P
Total for Item VII P
VIII. Airconditioning System
1 1.5 HP Window type, 4.00 units Pesos
Inverter, 220Vac, 1P,
60HZ, with ACU and ctvs.
Brackets (P ) / unit P
Doctors on Duty Room
Work Area Autoclave
Male Dressing Room
Female Dressing Room
2 2.0 HP Window type, 3.00 units Pesos
Inverter, 220Vac, 1P,
60HZ, with ACU and ctvs.
brackets (P ) / unit P
Chief Nurse Office
Premature Room
Labor Room
3 1.5 HP Split Inverter, 2.00 units Pesos
type, 220Vac, 1P,
60HZ, wall mounted, and ctvs.
Installation included, (P ) / unit P
w/ drain line, Cu tubings, insulation, outdoor breaker & ACU brackets
Pathologic Room
Nurse Station Work Area
4 2.0 HP Split Inverter, 5.00 units Pesos
type, 220Vac, 1P,
60HZ, wall mounted, and ctvs.
Installation included, (P ) / unit P
w/ drain line, Cu tubings, insulation, outdoor breaker & ACU brackets
Recovery Room - 1 unit
Operating Room - 2 units
Delivery Room -2 units
Item Description Quantity Unit Unit Cost Total Cost
No.
Total for ACU-S P
5 Electrical Works(Power line from
ACU To Main Panel board
w/ breaker)
a) 5.5mm2 THHN/THWN Wire 6.00 boxes Pesos
and ctvs.
(P ) / box P
b) 8.0mm2 THHN/THWN Wire 3.00 boxes Pesos
and ctvs.
(P ) / box P
c) Octagonal Box 24.00 Pcs. Pesos
and ctvs.
(P ) / pc. P
d) 20mm0 PVC Conduit 12.00 length Pesos
and ctvs.
(P ) / length P
e) 20mm0 Flexible 150.00 meters Pesos
Conduit
and ctvs.
(P ) / meter P
f) Breaker 9.00 Pcs. Pesos
and ctvs.
(P ) / pc. P
Total for Item 5 P
Total for Item VIII P
IX. Installation of Fire Protection System
I. Installation of Sprinkler System with Automatic Sprinkler
Item Description Quantity Unit Unit Cost Total Cost
No.
1 Sprinkler heads A1/2- NTP 41.00 pcs Pesos
Pendent, wet type,
Quick response, 165AF, and ctvs.
Bulb type w/ (P ) / pcs P
Escutcheon plate
2 B.I. Pipes 1.00 lot Pesos
25mmA˜, 32mmA˜,
40mmA˜, 50mmA˜, and ctvs.
65mmA˜, 75mmA˜ (P ) / lot P
3 B.I. Elbow 1.00 lot Pesos
25mmA˜,
32mmA˜, and ctvs.
40mmA˜, (P ) / lot P
75mmA˜,
4 B.I. Coupling 1.00 lot Pesos
25mmA˜, 32mmA˜,
40mmA˜, 50mmA˜, and ctvs.
65mmA˜, 75mmA˜ (P ) / lot P
5 Coupling Reducer 1.00 lot Pesos
(Threaded) -Sch-40
12mmA˜x 25mmA˜, and ctvs.
25mmA˜x 32mmA˜ (P ) / lot P
25mmA˜x 40mmA˜
40mmA˜x 65mmA˜
32mmA˜x 65mmA˜
32mmA˜x 50mmA˜
40mmA˜x 75mmA˜
6 B. I. End Cap 1.00 pcs Pesos
6.1 50mmA˜ B.I. Pipe Sch 40
welded and ctvs.
(P ) / pcs P
6.2 100mmA˜ isolation valve 1.00 pcs Pesos
(stem rising type)
(OR/DR Building) and ctvs.
(P ) / pcs P
7 Hanger Supports 1.00 lot Pesos
25mmA˜, 32mmA˜,
40mmA˜, 50mmA˜, and ctvs.
65mmA˜, 75mmA˜ (P ) / lot P
Item Description Quantity Unit Unit Cost Total Cost
No.
8 Misc. & Consumables 1.00 lot Pesos
(Fire Red Quick Drying
Paint Enamel, Paint and ctvs.
Thinner, Welding Rod (P ) / lot P
6011, Oxygen/
Acetylene, Gasket, Bolts & Nuts, Teflon Tape, Grinding Toner No. 20, Paint Brush 2-, 3-, A1/4-x2-x2- angle bar, 1/8-x1- flat bar, hanger rod 10mm0 with thread, anchor gript 3/8-x1 A1/2-, PVC, solvent cement, expansion shield, G. I. wire)
Total for Item I P
II. Supply of fire Hose Cabinet with Glass & Fire Extinguisher
1 Firehose Cabinet (Fire 1.00 set Pesos
Ax, Hose Double Jacket
30mx400mm with fog and ctvs.
Nozzle) with fire (P ) / set P
Extinguisher 4.5 kg Dry Chemical
Total for Item II P
Total for IX P
Total Bid Cost in Figures P
Total Bid Cost in Words
SUMMARY OF COSTS
Bid No. BVH-17-2335-NP (TF)
PROPOSED COMPLETION OF OR/DR COMPLEX AT BAROTAC VIEJO DISTRICT HOSPITAL
BAROTAC VIEJO, ILOILO
ITEM NO. Bid Amount
I) Removal/Installation of Roofings
(Including Re-painting of Existing Trusses) P
II) Ceiling Works (Including Removal of
Existing Ceiling) P
III) Tile Works (Including Removal of Existing Tiles) P
IV) Carpentry Works P
V) Painting Works P
VI) Room Signages P
VII) Electrical Works P
VIII) Airconditioning System P
IX) Installation of Fire Protection System P
TOTAL BID AMOUNT P
FORMS
Omnibus Sworn Statement
REPUBLIC OF THE PHILIPPINES )
ILOILO CITY ) S.S.
AFFIDAVIT
I, [Name of Affiant], of legal age, [Civil Status], [Nationality], and residing at [Address of Affiant], after having been duly sworn in accordance with law, do hereby depose and state that:
1. Select one, delete the other:
If a sole proprietorship: I am the sole proprietor of [Name of Bidder] with office address at [address of Bidder];
If a partnership, corporation, cooperative, or joint venture: I am the duly authorized and designated representative of [Name of Bidder] with office address at [address of Bidder];
2. Select one, delete the other:
If a sole proprietorship: As the owner and sole proprietor of [Name of Bidder], I have full power and authority to do, execute and perform any and all acts necessary to represent it in the bidding for [Name of the Project] of the [Name of the Procuring Entity];
If a partnership, corporation, cooperative, or joint venture: I am granted full power and authority to do, execute and perform any and all acts necessary and/or to represent the [Name of Bidder] in the bidding as shown in the attached [state title of attached document showing proof of authorization (e.g., duly notarized Secretary-s Certificate issued by the corporation or the members of the joint venture)];
3. [Name of Bidder] is not -œblacklisted- or barred from bidding by the Government of the Philippines or any of its agencies, offices, corporations, or Local Government Units, foreign government/foreign or international financing institution whose blacklisting rules have been recognized by the Government Procurement Policy Board;
4. Each of the documents submitted in satisfaction of the bidding requirements is an authentic copy of the original, complete, and all statements and information provided therein are true and correct;
5. [Name of Bidder] is authorizing the Head of the Procuring Entity or its duly authorized representative(s) to verify all the documents submitted;
6. Select one, delete the rest:
If a sole proprietorship: I am not related to the Head of the Procuring Entity, members of the Bids and Awards Committee (BAC), the Technical Working Group, and the BAC Secretariat, the head of the Project Management Office or the end-user unit, and the project consultants by consanguinity or affinity up to the third civil degree;
If a partnership or cooperative: None of the officers and members of [Name of Bidder] is related to the Head of the Procuring Entity, members of the Bids and Awards Committee (BAC), the Technical Working Group, and the BAC Secretariat,
the head of the Project Management Office or the end-user unit, and the project consultants by consanguinity or affinity up to the third civil degree;
If a corporation or joint venture: None of the officers, directors, and controlling stockholders of [Name of Bidder] is related to the Head of the Procuring Entity, members of the Bids and Awards Committee (BAC), the Technical Working Group, and the BAC Secretariat, the head of the Project Management Office or the end-user unit, and the project consultants by consanguinity or affinity up to the third civil degree;
7. [Name of Bidder] complies with existing labor laws and standards; and
8. [Name of Bidder] is aware of and has undertaken the following responsibilities as a Bidder:
a) Carefully examine all of the Bidding Documents;
b) Acknowledge all conditions, local or otherwise, affecting the implementation of the Contract;
c) Made an estimate of the facilities available and needed for the contract to be bid, if any; and
d) Inquire or secure Supplemental/Bid Bulletin(s) issued for the [Name of the Project].
9. [ Name of Bidder] did not give or pay directly or indirectly, any commission, amount, fee, or any form of consideration, pecuniary or otherwise, to any person or official, personnel or representative of the government in relation to any procurement project or activity.
IN WITNESS WHEREOF, I have hereunto set my hand this __ day of ___, 20__ at ___________________________, Philippines.
_____________________________________
Bidder-s Representative/Authorized Signatory
[JURAT]
Line Items
Item No.Product/Service NameDescriptionQuantityUOMBudget (PHP)
1Construction ProjectsPlease see attached1Lot6, 263, 545.00
Pre-bid Conference
DateTimeVenue
15/08/20189:00 AMBOARDROOM, OFFICE OF THE GOVERNOR, 3RD FLOOR, ILOILO PROVINCIAL CAPITOL, BONIFACIO DRIVE, ILOILO CITY
Closing Date : 2018-08-17

Documents

 Tender Notice


Similar Tenders

Request Demo
GiZ Tenders India

Procurement Documents for Philippines