Description
The Contractor shall provide all supervision, labor, equipment, and materials to inspect, repair, replace installed fire alarm system and associated connected devices with a like/in-kind system that meets requirements IAW ALL NFPA and UFC code requirements:
HMF-1 & HMF-2 BUILDINGS:
The contractor will replace the existing Notifier NFS-320 Fire Alarm Control Panel for Hangar HMF 1 & 2 with a new Notifier NFS-320 Control Panel. The contractor will install new Powersonic Batteries for the new fire alarm panel. The 120VAC will be rerouted in conduit outside of the Control Panel Enclosure. SOW. The contractor will provide and install one new Notifier NFS-320 Fire Alarm Control Panel. Remove the existing 120VAC wiring that is improperly running with the Low Voltage wire from inside the Control Panel Enclosure and install EMT Conduit to properly run the 120VAC wire to the correct side of the control panel to eliminate mixing with the existing Low Voltage wire inside the control panel enclosure. The contractor will conduct programming and Pre-Testing of all devices (100%) in accordance with NFPA 72 & UFC-3-601-02. IR detection in Hanger Decks must be tested with manufacture light gun as required by manufacturer. No magnets are allowed in testing any devices. Final Test with USCG Inspector and all work will be covered under Warranty for one year.
as per the Scope of Work in at USCG Base Elizabeth City, 1664 Weeksville Rd, Elizabeth City, NC 27909. detailed Statement of Work (SOW) is attached.
All quotes must be submitted by NOON Eastern Time on Aug 15, 2024. All quotes must be submitted via email to
[email protected]. Ensure blocks 14 (Include UEI) through 20c and 30a, 30b and 30c of the SF 1442, and pricing are completed before emailing.
Unit COR Jason Peck, (252) 335-6300 or
[email protected]This procurement is 100% set-aside for Small Businesses using NAICS code of 561621. The small business standard is 25 mil.
All elig...
Active Contract Opportunity
Notice ID : 70Z08124QELIZ0014
Related Notice
Department/Ind. Agency : HOMELAND SECURITY, DEPARTMENT OF
Sub-tier : US COAST GUARD
Office: BASE ELIZABETH CITY(00081)
General Information
Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
All Dates/Times are: (UTC-04:00) EASTERN STANDARD TIME, NEW YORK, USA
Original Published Date: Aug 07, 2024 08:57 am EDT
Original Date Offers Due: Aug 15, 2024 12:00 pm EDT
Inactive Policy: 15 days after date offers due
Original Inactive Date: Aug 30, 2024
Initiative: None
Classification
Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
Product Service Code: N063 - INSTALLATION OF EQUIPMENT- ALARM, SIGNAL, AND SECURITY DETECTION SYSTEMS
NAICS Code: 561621 - Security Systems Services (except Locksmiths)
Place of Performance: Elizabeth City, NC 27909 USA