The INDIAN ARMY has issued a Tender notice for the procurement of a Provn of Ring Main Unit at Kanchrapara Mil Stn, Qty: 280 in the India.The project location is North 24 Parganas, West Bengal, India. This Tender notice was published on 27 Nov 2026 and is scheduled to close on 07 Dec 2026, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 153162972 and Register on the platform.
Purchaser contact is for registered users
Login to see detailsTender details are for registered users
Login to see details| # | Title | Description | Qty | Unit | Delivery (Days) |
|---|---|---|---|---|---|
| 1 | Supply, install testing and commissioning of 4way non extensible outdoor type 11KV 630A rated switch gears with 2 Nos SF6 Circuit breaker and all as specified in pdf specification file | Supply install testing and commissioning of 4way non extensible outdoor type 11KV 630 Amp rated switchgears with two nos of SF6 circuit breaker as IC of capacity 630 Amp and two nos of LBS as O by G of capacity 630 Amp for outdoor applicationThe details of system parameters are as under- Network Three phases - Three wires Rated Voltage 12 kV Service Voltage 11kV System Frequency 50Hz Lightning Impulse withstand Voltage 75 kV p Phase to phase phase to earth 85 kV p Across the isolating distance 28 kV rms-1 min Power Frequency withstand voltage Rated Normal Current Line switch 630 A Transformer feeder 400 by 630 A Branch circuit breaker feeder 400 by 630 A | 3 | EACH Set | 120 |
| 2 | Material and labour for PCC 1-2-4 type B2 using 40 mm graded stone aggregate and all as specified in pdf specification file | Material and labour for PCC 1-2-4 type B1 using 40 mm graded stone aggregate for making good disturbed road surfaces including necessary use and waste of form work complete all as specified and directed. | 3 | cum | 120 |
| 3 | M and L for Earthing complete with galvanised steel pipe electrode 600 x 600 x 6 mm thick and all as specified in pdf specification file | M and L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground vertically in earth pit not less than 2.25 meters deep below ground level with top edge of plate not less than 1.5 metres below ground level, connected to and including GI Strip of size 25x4 mm and light grade protection pipe of 40 mm dia from earth electrode up to test point or up to 7.5 mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate No. 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade, GI funnel with wire mesh including charcoal and salt packed all around the earth electrode plate in layers, PCC earth pit chamber 1-3-6 type C1 of size 45x45x45 cm, RCC cover 1-2-4 type B1 of size 45x45x6 cm, excavation by earth work in any strata and returning filling, removal of surplus soil and testing by test point for required value complete including testing on completion all as specified and directed. GI strip up to 7.5m including testing considered in the item. | 6 | Each | 120 |
| 4 | Disconnecting existing HT Cable from GOD by LBS for the prepration and connection etc complete all as specified at site by Engr-in-charge | Disconnecting existing HT Cable from GOD by LBS for the prepration and connection etc complete all as specified at site by Engr-in-charge | 9 | Each | 120 |
| 5 | Excavation in trenches in soft by loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation etc and all as specified in pdf specification file | Excavation in trenches in soft by loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation etc. or for shaft, well, cesspits, manholes, fire hole, cable laying etc. n.exc 10 sqm on plan and not exceeding 1.5 mtr in depth and getting out complete all as specified and as directed by the Engineer-In-Charge. | 13 | Cum | 120 |
| 6 | Returning filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed by the Engineer-In-Charge. | Returning filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed by the Engineer-In-Charge. | 10 | cum | 120 |
| 7 | Removing excavated material not exce 50m and depositing directed at a level not exce 1.5 mtr above the starting pt complete all as specified and as directed by the Engr-In-Charge. | Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed by the Engineer-In-Charge. | 3 | cum | 120 |
| 8 | M and L for sand cushioning in trenches for protection of HV by LT underground cable including watering and consolidation. | M and L for sand cushioning in trenches for protection of HV by LT underground cable including watering and consolidation. | 3 | cum | 120 |
| 9 | Supplying and laying reinforced precast concrete cable cover, class HV, type 1 with peak of size 300mm x 180mm x 40mm in trenches for cable protection complete all as directed. | Supplying and laying reinforced precast concrete cable cover, class HV, type 1 with peak of size 300mm x 180mm x 40mm in trenches for cable protection complete all as directed. | 178 | Each | 120 |