Description
Product DescriptionAIR FILTRATION SYSTEM REQUIREMENTS (VENTILATED ENCLOSURE/PAINT BOOTH)
Many ventilation systems exist and could potentially be used to control the Cr(VI) hazard during aviationmaintenance processes.Selection should be done in collaboration with Industrial Hygiene and Safety professionals to ensure the ventilation system meets minimum design criteria.
Defense Centers for Public Health-Aberdeen recommends the following minimum design criteria:
• American Conference of Governmental Hygienists (ACGIH)® Industrial Ventilation Manual Figure VS-75-01 Large Paint Booth: Minimum cross-sectional velocity of 75 feet per minute (fpm) for a large deep booth with a cross-sectional area greater than 150 square feet (ft2). Airless electrostatic and high velocity low pressure spray paint operations require an air velocity of only 60 fpm.
• ACGIH® Industrial Ventilation Manual Figure VS-80-01 Abrasive Blasting Room: Cross-sectional velocity range of 60-100 fpm.
• American National Standards Institute/American Society of Safety Professionals (ANSI/ASSP) Z9.4-201 I (R2021): Requires a cross-sectional velocity of 80 fpm.
Exhaust System- 18, 000 Cubic Feet per Minute or higher to achieve ACGIH recommended TLVs- Must verify accurate testing and sampling data that system will provide clean air below the ACGIH TLVs of 0.0002mg/m3- Exhaust air to be “RETURNED TO BUILDING” as per ANSI Z9.7 (NO ADDITIONAL VENTILATION REQUIREMENTS TO ExISTING STRUCTURES)- Multi-stage Particulate filtration exceeds the National Emission Standards for Hazardous Air Pollutants (NESHAP) 319
Enclosure- Enclosure must be Cross Draft Negative- Material NFPA 701 Compliant- Recommend size: 10-H x 18-W x 45”L (based on hangar size and unit requirements)
Fire Suppression- Dry Chemical to protect both the enclosure and exhaust- Pre-engineered meeting NFPA 17 Standard for Dry Chemical extinguishing
Replacement Filters
- 18 Month Supply
Lighting ...
Active Contract Opportunity Notice ID W911SG24Q0074 Related Notice Department/Ind. Agency DEPT OF DEFENSE Sub-tier DEPT OF THE ARMY Major Command AMC Sub Command ACC Sub Command 2 MISSION & INSTALLATION CONTRACTING COMMAND Sub Command 3 418TH CSB Office W6QM MICC-FT BLISS
General Information
Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
All Dates/Times are: (UTC-06:00) MOUNTAIN STANDARD TIME, DENVER, USA
Original Published Date: Jun 14, 2024 02:28 pm MDT
Original Date Offers Due: Jun 26, 2024 10:00 am MDT
Inactive Policy: 15 days after date offers due
Original Inactive Date: Jul 11, 2024
Initiative: None
Classification
Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
Product Service Code: 4460 - AIR PURIFICATION EQUIPMENT
NAICS Code: 333413 - Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing
Place of Performance: Fort Bliss, Tx 79916 USA
Documents
Tender Notice