Procurement Summary
Country : Hong Kong
Summary : Supply and Installation of Power Supply, Uninterruptable for New Block Redevelopment Projects of Queen Man- Hospital and Cranlham Hospital
Deadline : 16 Nov 2022
Other Information
Notice Type : Tender
TOT Ref.No.: 73496091
Document Ref. No. : HKWC-T012/21(P-HKWC)
Financier : Self Financed
Purchaser Ownership : Public
Tender Value : Refer Document
Purchaser's Detail
Name :Login to see tender_details
Address : Login to see tender_details
Email : Login to see tender_details
Login to see detailsTender Details
Tenders are invited for Supply and Installation of Power Supply, Uninterruptable for New Block Redevelopment Projects of Queen Man- Hospital and Cranlham Hospital, Hong Kong West Cluster, Hospital Authority.
1 Introduction
1.1 The tender calls for the supply, delivery and installation, and
Testing and Commissioning for four (4) complete sets of
Uninterruptible Power Supply (UPS), Isolation Transformer,
Battery c/w Battery Monitoring System for Hospital Authority.
- 2 complete sets for Queen Mary Hospital
- 2 complete sets for Grantham Hospital
M
Part A Equipment Specification
2 General Description
2.1 Four (4) complete sets of Uninterruptible Power Supply (UPS)
shall include:
M
2.1.1 Uninterruptible Power Supply: 4 sets of online double
conversion modular UPS.
M
2.1.2 Isolation Transformer: 4 sets M
2.1.3 Battery completed with Battery Monitoring System: 4 sets M
2.1.4 Electrical and Others:
External Make-Before-Break Maintenance Bypass Panel
(EMBP): 4 sets
M
3 Specification for Uninterruptible Power Supply (UPS)
(Refer to Clause 2.1.1)
Each set of UPS shall have the following features:
M
3.1 Design
3.1.1 The UPS shall be designed and operated in Modular
Redundancy Architecture. It shall be made up of one or more
physically detachable equipment modules or cabinets, of drawout type and removable from the front of the UPS system.
Tenderers shall provide relevant information / specify the
requirements for equipment on offer in EOI return for
M
consideration. The Indicative UPS Schematic Diagram Drawing
would be provided in tender stage.
3.1.2 The UPS shall be dual feed input. M
3.1.3 The UPS shall be supplied with enough power module so that it
can support design load of following power rating in N+1
redundancy.
QMH: 140kW
GH: 200kW
M
3.1.4 Input Power Factor 0.99
Output Power Factor = 1
M
3.1.5 The control module and all power modules of the UPS Unit shall
be housed in single equipment rack.
M
3.1.6 Expandability:
In case future power expansion is needed, UPS Frame of
additional (minimum following power rating per frame and up
to 4 frames) shall be able to install to expand the UPS power
rating without power interruption to supporting load.
QMH: 140kW
GH: 200kW
M
3.1.7 Any installation or system reconfiguration required for the
expansion shall not affect the live operations of the modular
UPS. There is required to put the UPS onto bypass mode for
expansion.
M
3.1.8 The overall size of the UPS frame should not be larger than
900*2100*1200 (W*H*D in mm) per frame in all directions
M
3.1.9 The availability of the system shall not be less than 99.9995%. M
3.1.10 The current rating of the inter-battery cables shall be greater than
1.5x of the nominal maximum of charge / discharge current.
M
3.1.11 The rectifier / charger unit shall be provided with an input
isolating switch / circuit breaker.
The rectifier / charger unit shall have protection to prevent the
battery from over-charging due to battery charger / rectifier
fault. An adjustable battery current limiting device shall limit
the battery recharge current to the maximum value
recommended by the battery manufacturer.
M
The rectifier / charger unit shall be able to automatically adjust
the battery float charge voltage based on temperature variation
in accordance with battery manufacturer-s recommendation.
The charging current shall be adjustable from 5% to 30% so as
to limit the total input current when the battery has been
discharged.
3.2 Power Module:
3.2.1 Power Rating:
≥ 25kW per power module
The power modules shall be hot-swappable such that
replacement of the faulty modules can be carried out on-line
without any output interruption.
M
3.2.2 Features:
3.2.2.1 Soft Start and with Internal Backfeed Protection. M
3.2.2.2 UPS efficiency in double conversion mode ≥ 97% and shall be
able to maximize to 99% with energy save mode. (Self-declare
is not accepted, Manufacturer written literature with supporting
data required)
M
3.2.3 Input Voltage:
Three-phase 380V+N 50/60Hz
M
3.2.4 Input Voltage Range (V): 340 - 437 or wider M
3.2.5 Input Frequency : 40 to 70 Hz or wider M
3.2.6 Output Voltage:
Three-phase 380V+N 50/60Hz
M
3.2.7 Total voltage harmonic distortion: M
3.2.7.1 ≤ 1% (100% linear load) M
3.2.7.2 ≤ 5% (100% non-linear load) M
3.2.8 Overload on inverter: M
3.2.8.1 1 min from 125% M
3.2.8.2 10 seconds from 150% M
3.2.9 Permitted load power factor: 0.8 lagging to 0.8 leading M
3.2.10 Efficiency in double conversion On-Line mode ≥ 97%
Efficiency in Energy Saver Mode maximize to 99%
M
3.2.11 Energy efficiency of the UPS system shall not be less than 92%
at 50% rated load.
M
3.3 Internal Static Bypass Switch (SBP)
3.3.1 A full rating internal SBP shall be equipped for the UPS M
3.3.2 The SBP module shall be hot swappable M
3.3.3 The SBP shall be fuse and back feed protected M
3.3.4 Overload on bypass: M
3.3.4.1 110% continuous M
3.3.4.2 1000% 20 milliseconds M
3.4 UPS centralized communication module (UCM)
3.4.1 The UCM shall be hot swappable M
3.5 Battery Connection:
3.5.1 The UPS shall be ready for connecting to VRLA or Li-ion
Battery without any hardware modification nor additional cost.
M
3.6 Connectivity
3.6.1 Each UPS system shall equip with Simple Network
Management Protocol (SNMP v1 or v2) network adaptor for
remote monitoring through Ethernet network.
M
3.6.2 The UPS shall support TCP/IP and SNMP traps protocols for
remote monitoring. The network interface shall be Ethernet
10/100 Base T standard with RJ45 jack.
M
3.6.3 Each UPS system shall equip with: M
3.6.3.1 Mini-slot ports for optional cards M
3.6.3.2 Device USB and/or Host USB M
3.6.3.3 RS-232/RS-485/USB service port M
3.6.3.4 Relay output M
3.6.3.5 Output terminal/ connection for dummy load test (full load) and
battery discharge test
M
3.6.3.6 Building alarm inputs M
3.6.3.7 Emergency Power-Off (EPO) button status M
3.6.4 UPS system shall provide interfacing connections (e.g. SNMP,
Modbus, BACnet) to Central Control and Monitoring System
(CCMS), including but not be limited to:
- UPS status (on/off/fault)
- Static bypass status
- Internal static transfer switch status (not applicable to the UPS
for GH)
- Common fault alarm
- Input voltage(s)
- Input current(s)
- Input frequency
- Input power
- Output voltage(s)
- Output current(s)
- Output frequency
- Output power
- Output load rate (%) (not applicable to the UPS for GH)
- Bypass voltage (not applicable to the UPS for GH)
- Bypass current (not applicable to the UPS for GH)
- Battery voltage
- Battery temperature
- UPS input power supply failure
- UPS system failure
- Battery system failure
The tenderer shall be fully responsible for liaison and
coordination works with relevant parties including the Main
Contractor and other Mechanical and Electrical (M&E)
contractors for exact requirements and interfacing arrangement.
M
3.7 Standard Compliance
Equipment offered shall comply with:
M
3.7.1 Latest version of General Technical Specification for
Uninterruptible Power Supply (UPS), issued by Electrical and
Mechanical Services Department (EMSD)
M
3.7.2 Safety certification: IEC 62040-1 M
3.7.3 Electromagnetic compatibility (EMC) certification:
IEC 62040-2
M
3.7.4 Performance certification: IEC 62040-3 M Etc.
Documents
Tender Notice