Notice of intent to use a brand name product. The Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) is performing a market survey to determine if other potential sources of supply can provide a transformer protection relay that has equal performance requirements as the SEL-387L, manufactured by Schweitzer Engineering Laboratories (SEL), 2350 NE Hopkins Court, Pullman, WA 99163.
Fiscal Year 2027 SIOP PROJECT P-8026 ELECTRICAL BACKBONE Pearl Harbor Naval Shipyard and IMF Joint Base Pearl Harbor-Hickam, Hawaii, requires transformer protection relay that has equal performance requirements as the SEL-387L with the following characteristics:
Line Differential Protection - Protect transmission or distribution lines using current differential protection for high-speed clearing of internal line faults. Provide dual-slope differential elements with external fault security and communications-assisted protection for internal fault detection while maintaining stability during external faults.
Backup Protection - Provide comprehensive backup protection including phase, negative-sequence, and ground overcurrent elements, directional overcurrent elements, breaker failure protection, and configurable distance or permissive tripping functions as required for reliable line protection.
Line Monitoring - Monitor three-phase currents, voltages (when applicable), frequency, power, sequence quantities, and communications-assisted protection status. Provide fault location and disturbance analysis capabilities to support system operation and maintenance.
Reporting and Monitoring - Provide event reporting with sequential event recorder (SER), oscillographic event reports, fault records, and communications diagnostics to document faults, trips, currents, voltages, and relay operations for post-event analysis.
Panel Control Switches - Conveniently sized operator controls shall be located on the relay front panel and configured to track associated oper...
Notice ID: n6274226rsel387l
Department/Ind. Agency: dept of defense
Sub-tier: dept of the navy
Office: navfacsyscom pacific
Product Service Code: 5945 - relays and solenoids
NAICS Code: 335314 - Relay and Industrial Control Manufacturing
Inactive Dates: aug 14, 2026
Inactive Policy: 15 days after response date
Documents
Tender Notice