Notice of intent to use a brand name product. The Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) is performing a market survey to determine if other potential sources of supply can provide a transformer protection relay that has equal performance requirements as the SEL-351S-7, manufactured by Schweitzer Engineering Laboratories (SEL), 2350 NE Hopkins Court, Pullman, WA 99163.
Fiscal Year 2027 SIOP PROJECT P-8026 ELECTRICAL BACKBONE Pearl Harbor Naval Shipyard and IMF Joint Base Pearl Harbor-Hickam, Hawaii, requires the following characteristics.
Provide protection system relay with the following capabilities:
Feeder Protection - Protect distribution feeders using phase, ground, negative-sequence, and sensitive ground overcurrent elements. Provide instantaneous and time-overcurrent protection with configurable directional elements to detect and isolate feeder faults while maintaining system coordination.
Breaker Control and Protection - Provide breaker failure protection, autoreclosing, synch-check (when required), trip circuit monitoring, and integrated breaker control functions to improve system reliability and minimize outage duration.
Feeder Monitoring - Monitor three-phase currents, voltages, frequency, power, power factor, demand, and sequence quantities. Provide fault location, metering, and power quality information to support system operation, maintenance, and troubleshooting.
Reporting and Monitoring - Provide Sequential Events Recorder (SER), oscillographic event reports, fault records, and relay diagnostics to document faults, trips, breaker operations, currents, voltages, and relay performance for post-event analysis.
Panel Control Switches - Conveniently sized operator controls shall be located on the relay front panel and configured to track associated operator control functions, including breaker open/close control, relay status indication, and programmable pushbutton operations.
This notification...
Notice ID: n6274226rsel351s7
Department/Ind. Agency: dept of defense
Sub-tier: dept of the navy
Office: navfacsyscom pacific
Product Service Code: 5945 - relays and solenoids
NAICS Code: 335314 - Relay and Industrial Control Manufacturing
Inactive Dates: aug 14, 2026
Inactive Policy: 15 days after response date
Documents
Tender Notice