Per SCAF dated March 2025; Equipment must, as a minimum, be labelled for arc flash hazards per CSA C22.1-24 Clause 2-306 (1) & (2). Recommend replacing the circuit breakers and panels 1E, 1F, 1G, 1H, 1J, 2F, BA and panel AA(elevator circuit breaker) due to insufficient short circuit fault ratings. Recommend having the interrupting rating on Panel AA nameplate once the replacement of the breakers has been implemented.
Solicitation Type : RFQ - Request for Quote (Formal) Reference Number : 0000328582 Location : Canada, Newfoundland and Labrador, Avalon Region Delivery Point : Bldg. 223, 99 Churchill Avenue, Pleasantville, St. John's, NL Purchase Type : One Time Only- Delivery Date:Jan 29, 2027 Description : Per SCAF dated March 2025; Equipment must, as a minimum, be labelled for arc flash hazards per CSA C22.1-24 Clause 2-306 (1) & (2). Recommend replacing the circuit breakers and panels 1E, 1F, 1G, 1H, 1J, 2F, BA and panel AA(elevator circuit breaker) due to insufficient short circuit fault ratings. Recommend having the interrupting rating on Panel AA nameplate once the replacement of the breakers has been implemented.