Cross Icon
Cross Icon

Fire Suppression Tender in USA - 5319884

The DEPARTMENT OF THE AIR FORCE has issued a Tender notice for the procurement of a Fire Suppression in the USA. This Tender notice was published on 15 Feb 2016 and is scheduled to close on 18 Feb 2016, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 5319884, while the tender notice number is F2X3CE6025A002 and Registering on the platform.

Expired Tender

Procurement Summary

Country: USA

Summary: Fire Suppression

Deadline: 18 Feb 2016

Posting Date: 15 Feb 2016

Other Information

Notice Type: Tender

TOT Ref.No.: 5319884

Document Ref. No.: F2X3CE6025A002

Competition: ICB

Financier: Self Financed

Purchaser Ownership: -

Tender Value: Refer Document

CPV Classification

35111500 - Fire suppression system

Purchaser's Detail

Name: Login to see tender_details

Address: Login to see tender_details

Email: Login to see tender_details

Login to see details

Tender Details

1.0 description of items. The contractor shall provide all material, and labor to install automatic sprinkler fire suppression systems for one (1) 4, 500 sq ft k-span assembly facilitiy, eight (8) 968 sq ft lodging facilities, and six (6) 660 sq ft lodging facilities at the vigiliant warrior camp in titus, alabama. The contractor shall provide an automatic sprinkler fire suppression system for each facility, for a total of fifteen (15) systems.
1.1 clin0001: the contractor shall provide and install one (1) automatic sprinkler fire suppression system in a 4, 500 sq ft assembly facility. . at a minimum the automatic fire suppression system must meet the requirements specified in sor paragraphs 1.1.1 - 1.1.11.
1.1.1 wet pipe fire automatic sprinkler systems suppression system

1.1.2 starting at a 4 inch ductile iron stub up water supply inside facility

1.1.3 properly engineered and installed automatic sprinkler systems will be designed to detect the presence of fire and distribute water in sufficient quantity to either control or extinguish the fire.

1.1.4 sprinkler systems must use equipment and devices listed by a nationally recognized testing laboratory (nrtl)

1.1.5 the sprinkler system must be designed to meet the area/density method of national fire protection association standard 13 (nfpa 13)

1.1.6 the government will not accept galvanized piping.

1.1.7 new sprinkler systems protecting areas of 1, 500 ft2 (139 m2) and greater must be designed using hydraulic calculations. Use of pipe schedule designs is strongly discouraged for any sprinkler system. Required discharge densities and areas of discharge operation are given in paragraph sprinkler density and hose stream requirements. Calculations must follow the format of nfpa 13. Pipe friction losses and equivalent lengths of pipe for fittings and valves must be in accordance with nfpa 13.

1.1.8 sprinklers must provide coverage throughout 100 percent of the building except as permitted by nfpa 13.

1.1.9 plain end fittings with mechanical couplings and fittings that use steel gripping devices to bit into the pipe are prohibited.

1.1.10 steel piping with wall thickness less than schedule 40 shall not be threaded.

1.1.11 piping must hang on tabs shown (see appendix a)

1.2. Clin0002: the contractor shall provide and install one (1) automatic sprinkler fire suppression system for eight (8) 968sq ft facilities and six (6) 660sq ft facilities. At a minimum each automatic fire suppression system must meet the requirements specified in sor paragraphs 1.2.1 - 1.2.9.
1.2.1 wet pipe automatic sprinkler systems fire suppression system

1.2.2 starting at a 2 inch copper stub up water supply inside facility (see appendix b)

1.2.3 properly engineered and installed automatic sprinkler systems will be designed to detect the presence of fire and distribute water in sufficient quantity to either control or extinguish the fire.

1.2.4 sprinkler systems must use equipment and devices listed by a nrtl

1.2.5 provide sprinkler systems that are designed using the area/density method of nfpa 13

1.2.6 galvanized piping is not permitted

1.2.7 sprinklers must provide coverage throughout 100 percent of the building except as permitted by nfpa 13.

1.2.8 plain end fittings with mechanical couplings and fittings that use steel gripping devices to bit into the pipe are prohibited.

1.2.9 steel piping with wall thickness less than schedule 40 shall not be threaded.
2.0 installation requirements: the contractor shall install fire suppression system on location at the vigiliant warrior camp located in titus, alabama.
2.1 the contractor shall provide and install all wiring, connectors and hardware, as required to complete the work. All wiring must be installed in a neat and professional manner.
2.2 the contractor shall provide customer with all books, manuals, literature, cds and dvds and other documentation on all equipment installed. Provide customer with all programming source code, to include but not limited to uncompiled source code, panel files, ir/232/ip modules, and any other digital or software requirement for full utilization, operation, and maintenance of system.
2.3 the contractor must provide all building modifications required to complete this project (electricity, conduit, and plumbing). Must work with base agencies where approval is required and provide documentation of applicable changes. Contractor will coordinate all building modifications with the contracting officer to eliminate or minimize disruptions.
2.4 the contractor is responsible for post construction cleanup, which will include removal of all material, packaging, and all other debris left as a result of construction. General clean-up of material, packaging, and work areas will be conducted during job progress (at the end of each day as a minimum) to minimize unacceptable appearance of job site to to visitor populations. Contractor will be responsible for any damages to facility caused by contractor and personnel. Installation should take no longer than two months.
2.5 the contractor shall be responsible for any and all high voltage and low voltage electrical work, and plumbing required to complete installation. The contractor will be responsible for any and all interior or exterior construction required.
3.0 performance management plan (pmp): the contractor shall provide a pmp that shows a timeline from issuance of the contract to delivery of the fire suppression systems to the delivery location identifed in this solicitation. The pmp may be expressed in terms of "days after contract". This pmp shall include, at a minimum, a timeline for:
description days after contract

ordering

delivery

installation
4.0. Warranty: the contractor must provide manufacturers warranties for the products supplied by the contractors. A ninety one-year quality of installation warranty to insures that the installation is satisfactory and if any errors were made or any problems occur, the customer will have one-year to identify the issues. The contractor is responsible for fixing or replacing any issues with system within a one-year period from installation completion at no additional cost to the government.
5.0 general information: system must be complete and usable upon completion. Items must be brand new. Refurbished items are not authorized. All material submitted for consideration shall meet the requirements of the unified facilities criteria (ufc) 3-600-01. Complete automatic sprinkler protection must be provided in accordance with nfpa 13 sprinkler systems. Design shall meet or exceed all codes, regulations, and guidelines set forth by nfpa 13, nfpa 72, and nfpa 101, along with any state and local regulations.
Appendices
1. Appendix a: assembly drawings

2. Appendix b: lodging drawings
please consult the list of document viewers if you cannot open a file.

Fire suppression

type: other (draft rfps/rfis, responses to questions, etc..) label:

fire suppression

posted date: february 11, 2016 fire_suppression_statement_of_requirements.pdf (185.95 kb)

description: fire suppression_statement of requirement
titus, alabama

titus, alabama 36080

united states
primary point of contact.:

monica philpot,

contract specialist

[email protected]

phone: 334-953-3528secondary point of contact:

marcus abram,

contract specialist

[email protected]

phone: 334-953-3526

fax: 334-953-3527 all files

fire suppression

feb 11, 2016

fire_suppression_sta...download/view fire_suppression_statement_of_requirements.pdfgeneral information
marcus abram,

contract specialist

[email protected]

phone: 334-953-3526

fax: 334-953-3527 all files

fire suppression

feb 11, 2016

fire_suppression_sta...download/view fire_suppression_statement_of_requirements.pdfgeneral information

notice type:

sources sought

posted date:

february 11, 2016

response date:

feb 18, 2016 11:59 pm eastern

archiving policy:

automatic, 15 days after response date

archive date:

march 4, 2016

original set aside:

n/a

set aside:

n/a

classification code:

12 -- fire control equipment

naics code:

333 -- machinery manufacturing/333999 -- all other miscellaneous general purpose machinery manufacturing

for help: federal service deskaccessibility
12 -- fire control equipment

naics code:

333 -- machinery manufacturing/333999 -- all other miscellaneous general purpose machinery manufacturing
333 -- machinery manufacturing/333999 -- all other miscellaneous general purpose machinery manufacturing

for help: federal service deskaccessibility

added: feb 11, 2016 12:07 pm

Documents

 Tender Notice


Similar Tenders

Request Demo
GiZ Tenders India

Procurement Documents for USA

Access a comprehensive library of standard procurement documents specific to USA. Here, you'll find all the essential forms, guidelines, and templates required for tender applications and submissions in USA

Explore Procurement Documents for USA


Want To Bid in This Tender?

Get Local Agent Support in USA and 60 More Countries.

View All The Services


View Tenders By


Publish Tenders


Have Any Dispute With The Purchaser?