Page 12 of 12
Page 1 of 14
STATEMENT OF WORK
CONTRACT TITLE: Fire Sprinkler repairs
PLACE OF PERFORMANCES:
VA San Diego Healthcare System
3350 La Jolla Village Dr.
San Diego, CA 92161
PERIOD OF PERFORMANCE: 07/01/2026-06/30/2027
CONTRACT TYPE:
Firm Fixed Price
BACKGROUND: Fire sprinkler deficiencies from 2025 annual inspection and testing.
GENERAL REQUIREMENTS:
Per applicable VA San Diego requirements/standards, the contractor will:
BLDG 1 WETPIPE REQUIRED REPAIRS:
**** 6TH FLOOR ****
NORTH: The following areas were found to have 50yr old sprinklers: 6231 (2), 6232 (2), 6233A (2), 6242 (2), 6239 (2), 6240, 6233 (2), 6243 (2), 6254 (6), 6245 (2), 6246 (4), 6246A (2), 6230 (4), 6252B (2), 6252C (1), 6252E (4), 6247 (2), 6249 (2), 6250 (1), 6251 (1), 6254 (6), 6254A (2), 6256 (2), 6257 (2), 6264 (1), 6254B (2), 6263 (2), 6267 (6), 6268 (1), 6269 (2), 6259 (2), 6263A (1), 6224 (1), 6225 (1), 6219 (2), 6218 (2), 6217 (4), 6215 (1), 6268 (2). Replace (88) 165° STD ½ Chrome SSP 401chrome trim.
WEST: The following areas were found to have 50yr old sprinklers: 6097 (1), 6024 (1), 6035 (4), 6025 (2), 6032 (2), 6030(4), 6070 (1), 6029 (2), 6083 (2), 6082 (2), 6050 (1), 6045 (2), 6080 (1), 6081 (14), 6062 (3), 6048 (2), 6051 (2), 6049 (2), 6052(5), 6055 (3), 6058 (2), 6061 (2), 6056A (2), 6069 (2), 6074 (2), 6086 (2), 6087 (2), 6088 (4), 6095 (2), 6096 (2), 6091 (1), 6091A(1). Replace (82) 165° STD ½ chrome SSP 401 chrome trim.
SOUTH: The following areas were found to have 50yr old sprinklers: 6105 (3), 6107 (4), 6110 (4) 6118 (2), 6112 (1). Replace(14) 165° STD ½ chrome SSP 401 chrome trim. EAST: The following areas were found to have 50yr old sprinklers: 6149 (1), 6150 (4), 6153 (2), 6160 (1), 6163 (2), 6164 (4), 6169 (2), 6170 (2), 6171 (2), 6172 (2), 6176 (2), 6174C (3), 6174G (4), 6174F (4), 6184 (2), 6189A (3), 6189C (2), 6187 (1), 6190(1), 6191 (2), 6192 (2), 6197 (1), 6198 (2), 6200 (3), 6202 (...
Notice ID: 36c26226q0654
Department/Ind. Agency: veterans affairs, department of
Original Set Aside: service-disabled veteran-owned small business (sdvosb) set-aside (far 19.14)
Sub-tier: veterans affairs, department of
Office: 262-network contract office 22 (36c262)
Product Service Code: j012 - maint/repair/rebuild of equipment- fire control equipment
NAICS Code: 238220 - Plumbing, Heating, and Air-Conditioning Contractors
Inactive Dates: jul 19, 2026
Inactive Policy: manual
Documents
Tender Notice
Documents.zip