Cross Icon
Cross Icon

Electrical Panel Tender in Canada - 143231629

The P-3-SP-$ STRATEGIC PROCUREMENT/APPROVISIONNEMENT STRATÉGIQUE has issued a Tender notice for the procurement of a Electrical Panel in the Canada. This Tender notice was published on 13 Jun 2026 and is scheduled to close on 22 Jun 2026, with an estimated Tender value of Refer Document. Interested bidders can access detailed Tender information, eligibility criteria, and complete bidding documents by referencing TOT Ref No. 143231629, while the tender notice number is 0677007-27 and Registering on the platform.

Expired Tender

Procurement Summary

Country: Canada

Summary: Electrical Panel

Deadline: 22 Jun 2026

Posting Date: 13 Jun 2026

Other Information

Notice Type: Tender

TOT Ref.No.: 143231629

Document Ref. No.: 0677007-27

Competition: ICB

Financier: Self Financed

Purchaser Ownership: Public

Tender Value: Refer Document

Purchaser's Detail

Name: Login to see tender_details

Address: Login to see tender_details

Email: Login to see tender_details

Login to see details

Tender Details

Tender are invited for Electrical Panel
Tender Details *****Amendment #6*****
Please be advised that this Invitation to Tender (ITT) has been amended to provide an updated Service Entrance Board specification and Electrical Drawing, see attached. The changes include the following:
1. Service entrance board rating shall be increased from 1600A to 2000A, with short circuit current rating of 42 kA (rms symmetrical).
2. Service entrance board main breaker shall have 100% rated 2000A breaker c/w solid state trip sized for 2000A.
3. Main breaker shall be c/w ground fault protection.
4. 2000A, 600V panel 6DPA:
a. Add one 100A, 3P breaker
b. Add two 800A, 100% rated breakers
5. 800A, 208V panel '2DPA':
a. Add one 60A, 3P breaker
6. 800A, 208V panel '2DPB':
a. Add one 60A, 3P breaker
All other information remains the same
***
*****Amendment #5*****
Please be advised that this Invitation to Tender has been amended to EXTEND the closing date to June 22, 2026.
All other information remains the same
***
*****Amendment #4*****
Please be advised that this Invitation to Tender (ITT) has been amended to provide the following information:
1. In the 800A, 208V panel '2DPB':
a) Change one 150A, 3P breaker to 100A, 3P
b) Change one 40A, 3P breaker to 30A, 3P
c) Change one 40A, 3P breaker to 60A, 3P
d) Change one 40A, 3P breaker to 100A, 3P
2. In the 1600A, 600V panel 6DPA:
a) Change 250A, 3P breaker for MCC-1 to 300A, 3P
All other information remains the same
***
*****Amendment #3*****
Please be advised that this Invitation to Tender (ITT) has been amended to answer the following Bidder(s) questions:
Q1: Can you confirm if you are expecting the Switchboard Pricing to include the price of an Arc Flash Study as described in 26...

Documents

 Tender Notice


Request Demo
GiZ Tenders India

Procurement Documents for Canada

Access a comprehensive library of standard procurement documents specific to Canada. Here, you'll find all the essential forms, guidelines, and templates required for tender applications and submissions in Canada

Explore Procurement Documents for Canada


Want To Bid in This Tender?

Get Local Agent Support in Canada and 60 More Countries.

View All The Services


View Tenders By


Publish Tenders


Have Any Dispute With The Purchaser?