Summary: Defense Supply Center Richmond B46 Generator Tie In
Deadline: 02 Jun 2026
Posting Date: 23 May 2026
Other Information
Notice Type: Tender
TOT Ref.No.: 141892283
Document Ref. No.: SP470326B0001
Competition: ICB
Financier: Self Financed
Purchaser Ownership: Public
Tender Value: Refer Document
Purchaser's Detail
Name: Login to see tender_details
Address: Login to see tender_details
Email: Login to see tender_detailsLogin to see details
Tender Details
Update 22 May 2026:
Corrected error on page 1 of IFB solicitation. Block 13 now has the X for the bid guarantee. This was called out in FAR 52.228-1. 20% bid guarantee required. See new solicitation document in the attachements. IFB extended to 2 June 2026, end of day. Bid opening 3 June 2026 at 10am. See below.
There appears to be a conflict between the one-line diagram on Sheet E-602 and the new work power plan on Sheet E-110 regarding the secondary feeder from XFMR T58 to ATS-B.
On E-602, this feeder is identified as 3200.4 (9 sets of 4-#500 KCMIL, 4" conduit), which per the feeder schedule appears to indicate new conduit installation. However, Sheet E-110 references Keynote 2 along the same routing, which directs conductors to be installed within existing underground conduits, consistent with the parallel T57-to-ATS-A feeder identified as 3200.4U.
Please confirm whether the T58-to-ATS-B feeder is intended to:
Reuse existing underground conduit infrastructure, in which case the feeder designation should read 3200.4U; or
Be installed in new conduit, in which case Keynote 2 would not apply to this feeder run.
Answer: The intent is to reuse the existing conduit infrastructure for the T58 to ATS-B feeder. That feeder on E-602 should have been identified as 3200.4U.
RFI's:
All building power outages are to take place on weekends, holiday breaks, or times when there will be no occupants in the building.
Correct. As this building will be occupied, we cannot have power interruptions during normal working hours.
Please confirm per the site visit comments - Contractor is not required to provide backup generators or backup power for weekend outages to take place.
Confirmed. The contractor is not required to provide a backup generator or power for weekend outages.
------------
Update: Revised Attachment 1 - Plans attached. See redaction on page E-001 removing specific language about the portable generator.
---...
Notice ID: sp470326b0001
Department/Ind. Agency: dept of defense
Original Set Aside: total small business set-aside (far 19.5)
Sub-tier: defense logistics agency
Office: dcso richmond division #1
Product Service Code: j061 - maint/repair/rebuild of equipment- electric wire and power distribution equipment
NAICS Code: 238210 - Electrical Contractors and Other Wiring Installation Contractors
Inactive Dates: jun 17, 2026
Inactive Policy: 15 days after date offers due