Procurement Summary
Country: USA
Summary: Building 65 Switch 1 Repair at Vamc Central Western Ma
Deadline: 05 Aug 2026
Posting Date: 04 Aug 2026
Other Information
Notice Type: Tender
TOT Ref.No.: 146492173
Document Ref. No.: 36C24126Q0671
Competition: ICB
Financier: Self Financed
Purchaser Ownership: Public
Tender Value: Refer Document
Purchaser's Detail
Name: Login to see tender_details
Address: Login to see tender_details
Email: Login to see tender_detailsLogin to see details
Tender Details
AMENDMENT NO. 2
SOLICITATION NO. 36C24126Q0671
DATE: 8/3/2026
This amendment is issued to inform all interested vendors of the following changes to the solicitation:
1. Inclusion of Electrical One-Line Diagram
The solicitation is updated to include the attached medium-voltage electrical one-line diagram (Campus Electrical online working copy.pdf 12.23.25), which provides a comprehensive overview of the site s electrical distribution system. Vendors are advised to review this diagram for details on system configuration, isolation points, and load connections.
2. Responses to Request for Information (RFI):
Switch 1 s Upstream Source, Isolation Points, and Downstream Loads:
Please see the attached Switch 1 diagram for its upstream source and isolation points. Downstream loads include B65 breaker, SW2, and TR15 (1500KVA 13.8KV TO 480/277V).
Alternate, Emergency, or Potential Backfeed Sources:
Building 15 (B15) is equipped with an Automatic Transfer Switch (ATS) and generator, providing emergency and alternate power sources.
Responsibility for Operating Upstream Medium-Voltage Equipment (Switching, LOTO, Grounding, Restoration):
As stated in the Statement of Work (SOW), the contractor is responsible for all switching and Lockout/Tagout (LOTO) procedures, including grounding and restoration of upstream medium-voltage equipment. VA personnel will not perform these operations.
Arc-Flash Information, Protective-Device Settings, and Outage Impact:
All arc-flash values, protective-device settings, and outage-impact details must be verified in the field. For planning purposes, assume arc-flash values are less than or equal to 40 Cal/cm².
VA Electrical-Shop Support During Shutdown:
VA electrical-shop support will not be available during the shutdown.
3. Extension for Due Date of Quotes
The due date for the submission of quotes has been extended.
New Due Date: August 5, 2026
Time: 4:00 PM EST
4. All other terms a...
Notice ID: 36c24126q0671
Department/Ind. Agency: veterans affairs, department of
Sub-tier: veterans affairs, department of
Office: 241-network contract office 01 (36c241)
Product Service Code: j061 - maint/repair/rebuild of equipment- electric wire and power distribution equipment
NAICS Code: 238210 - Electrical Contractors and Other Wiring Installation Contractors
Inactive Dates: sep 04, 2026
Inactive Policy: manual
Documents
Tender Notice