Procurement Summary
Country : USA
Summary : 30 CES - Pad Mount Transformers (2 of 2)
Deadline : 30 May 2025
Other Information
Notice Type : Tender
TOT Ref.No.: 119167696
Document Ref. No. : FA461025Q0034
Financier : Self Financed
Purchaser Ownership : Public
Tender Value : Refer Document
Purchaser's Detail
Name :Login to see tender_details
Address : Login to see tender_details
Email : Login to see tender_details
Login to see detailsTender Details
Description
Five (5) phase pad-mounted transformers shall have the following voltage ratings: •112.5 KVA, 208Y/120, 12 kV•150 KVA, 480Y/277, 12 kV•300 KVA, 480Y/277, 12 kV•500 KVA, 480Y/277, 12.47 kV•750 KVA, 480Y/277, 12 kV In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below: •All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.), stainless-steel grade shall be 304L or 316L (if available).•"Pentahead" cabinet locking mechanism/device.•Dead-Front construction (HV-200A load break elbows with shield adapters).•Externally clamped LV bushings with threaded copper stud for full load current below 2, 100.amperes - NEMA spades shall be provided per ANSI hole requirements.•Radial feed or Loop feed•Frequency: 60Hz.•Windings: HV/LV copper•Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.•Standard impedance.•Mild steel high-voltage/low-voltage compartment barriers.•Cooling fins.•Proper grounding provisions.•Dial type gauges for oil temperature, liquid level and pressure/vacuum.•Bay-O-Net fuses & current-limiting fuses: properly sized - additionally, the transformer shouldbe equipped with three spare fuses.•Two-position "ON/OFF" load break primary switch•5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%)•Automatic pressure relief device mounted on the terminal compartment.•Oil drain valve with sampling device, and an oil-fill/oil-level plug.•Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate.•Compliant with 2016 DOE Efficiency Standard.•Four (4) lifting lugs. •Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish.•Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions.•Provide DGA test to verify conformance to performance requirements as outlined in the latestre...
Active Contract Opportunity
Notice ID : FA461025Q0034
Related Notice
Department/Ind. Agency : DEPT OF DEFENSE
Sub-tier : DEPT OF THE AIR FORCE
Office: FA4610 30 CONS PK
General Information
Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
Original Published Date: May 14, 2025 10:35 am PDT
Original Date Offers Due: May 30, 2025 01:00 pm PDT
Inactive Policy: 15 days after date offers due
Original Inactive Date: Jun 14, 2025
Initiative: None
Classification
Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
Product Service Code: 6120 - TRANSFORMERS: DISTRIBUTION AND POWER STATION
NAICS Code: 335311 - Power, Distribution, and Specialty Transformer Manufacturing
Place of Performance: Lompoc, CA 93437 USA
Documents
Tender Notice
Atch-3_ClausesProvisions.pdf
Atch-1_Transformers_SOW.pdf
Transformers_RFQ.pdf
Atch-2_PricingSheet.xlsx