Procurement Summary
Country : Philippines
Summary : Provision of Fire Protection System (FDAS, FSS, Emergency Lights and Signages) at Roxas Airport - Reposting
Deadline : 13 Aug 2018
Other Information
Notice Type : Tender
TOT Ref.No.: 25046323
Document Ref. No. : GO2018-07-012
Competition : ICB
Financier : Self Financed
Purchaser Ownership : -
Tender Value : Refer Document
Purchaser's Detail
Purchaser : CIVIL AVIATION AUTHORITY OF THE PHILIPPINES - ROXAS AIRPORT
NEIL GALINDO ARGONCILLO
BAC Secretariat
CAAP, Roxas Airport
CAPIZ
Roxas City
Capiz
Philippines 5800
63-36-6210991
63-36-6212249
caap.ccc@yahoo.com
Philippines
Email :caap.ccc@yahoo.com
Tender Details
Provision of Fire Protection System (FDAS, FSS, Emergency Lights and Signages) at Roxas Airport - Reposting
see attached
Line Items
Item No.Product/Service NameDescriptionQuantityUOMBudget (PHP)
1Provision of Fire Protection SystemSupplyof labor, equipment/tools, and material testing for the Provision of Fire Protection System (FDAS, FSS, Emergency Lights, and Signages) at Roxas Airport1Lot997, 780.88
Other Information
1.00 FIRE PROTECTION WORKS
A Materials
1.01 Fire Detection and Alarm System
1.00 set Multi-zone Addressable Fire Alarm Control Panel with Back-up Batteries and other Accessories. 1-4 loops, Multiple device (up to 1000 addressable devices)
Power Supply : 230 Vac A+/- 10%, 50/60 Hz, 0.97A max.
Batteries : 24 Vdc, 2.47 A max. charging current
Operating Environment : 0Eš-49EšC, 1-93% RH
1.00 Set Addressable Combination Smoke & Heat Detector with base, Approx. 100mm x 58mm
Operating Environment : 0Eš-49EšC, 0-93% RH
Fixed Temperature Rating :57.2EšC; Actual Alarm Point: 53.9-60.6EšC
38.00 sets Addressable Smoke Detector with Base, Approx. 100mm x 58mm
Operating Environment : 0Eš-49EšC, 0-93%RH
12.00 sets Fire Alarm Horn w/ Strobe, Approx. 140mm x 140mm
Rated Strobe Output : 15-110 cd (candela)
Strobe Flash Rate : Synchronized at one (1) flash per second
Operating Environment : 0Eš-49EšC ambient temperature
6.00 sets Manual Pull Station, 28 Vdc, 1.0 A
2.00 sets Input Signal Module for Horn/Strobes
Operating Current : 223I1/4A (Standby), 100I1/4A(Activated)
1.02 Conduits and Fittings
163.00 pcs 20mm diameter x 3m EMT Pipe
2.00 rolls 15mm diameter Flexible Metal Conduit x 30m
26.00 pcs 20mm diameter EMT Elbow
94.00 pcs 20mm diameter EMT Coupling
203.00 pcs 20mm diameter EMT Connector
11.00 pcs 15mm x 10mm x 2.44m PVC Moulding
1.03 Wires & Cables
1.00 roll 3.5 mm2 THHN/THWN-2 x 150m Copper Wire (UL Listed)
6.00 rolls 1.25 mm2 TF x 150m Copper Wire (UL Listed)
4.00 rolls 1.25 mm2 Twisted Pair x 150m Copper Wire (UL Listed)
1.04 Electrical Wiring Devices
5.00 sets Single Convenience Outlet with plate and bracket - 10A, 250V, Universal type w/ ground
1.05 Emergency Light and Signages
5.00 pcs 2x3 Watts, 230V, 60Hz LED Emergency Light (3 hours emergency operation)
6.00 pcs 5 Watts, 230V, 60Hz LED Exit Sign with acrylic plastic light diffuser Wall/Ceiling mounted and 3 hours emergency operation (Verify Arrow direction on the plans)
1.06 Boxes & Pullboxes
68.00 pcs Junction Box with cover Gauge 16 (Steel)
1.00 pc Pullbox, 200mmx200mmx100mm Gauge 16
1.07 Termination Accessories
2.00 pcs Electrical Tape, 19mmx0.19mmx16m
1.00 pc PVC Solvent Cement 400cc
1.08 Fire Extinguisher
14.00 pcs 10 lbs HCFC-123 ABC Multi-Purpose Portable Fire Extinguisher with complete accessories
1.09 Ceiling Board
10.00 pcs 4.5mm thk x 4- x 8- Fiber Cement Board
2.00 gal Flat Latex Paint
1.00 gal Latex Paint
1.00 kg Powdered Joint Compound
1.00 pc Paint Roller 9- with pan
1.00 pc Paint Brush, 4-
1.00 kg Rugs
4.00 pcs Sand Paper #120
1.00 roll Mesh Tape
B 1.00 lot Labor
C Equipment Rental
QTY DAYS
2.00 28 Steel Scaffold includes H-Frame, Cross Braces, Stage and Ladder
SCOPE OF WORKS:
The project covers the supply of labor, materials, tools/equipment-s and construction related permits necessary for the Provision of fire Protection System (FDAS, FSS, Emergency Lights and Signages) with the following scopes of work which shall be done in accordance with the approved plans, specifications and provision of contract to wit:
I. FIRE PROTECTION WORKS
The work includes the supply of materials, labor, equipment/tools, and material testing to complete the installation of the following: Fire Detection and Alarm System, Electrical Conduits & Fittings, Wires & Cables, Electrical Wiring Devices, Emergency light and Signage, Boxes & Pull boxes, Termination Accessories and Fire Extinguisher as indicated on the plans. Fire Protection Works should be tested and commissioned.
The work also includes the supply of materials, labor, and equipment/tools to complete the restoration of damaged ceiling including repainting works needed for the access in lay-outing of conduit pipes.
All scopes of work to this item must be according to plans and specifications and approved by the Project Engineer. Also, quality and types of materials must conform and must be approved by the Project Engineer.
The contractor shall be responsible in providing safety perimeter fence or security fences, personal protective equipment (PPE) for staffs and workers, and Safety Inspectors or Safety Engineers on site while construction is ongoing. Regular safety reports should be accomplished.
The contractor shall be responsible for all laboratory, material testing environmental compliance certificate (ECC), building and safety permits and survey instruments necessary in the project implementation. All expenses shall be incorporated in the contractor-s overhead cost and shall not be considered as pay item.
Note: The Contract includes all works and services although not specifically mentioned herein, but are needed to fully complete the Project.
Closing Date : 2018-08-13
Documents
Tender Notice